Chapter 5 Function parameter
36
PA-02
PID feedback source
0
:
AI1
1
:
AI2
2
:
AI3/ Panel potentiometer
3
:
AI1-AI2
4
:
Pulse setting
(
X6
)
5
:
Communication given
6
:
AI1+AI2
7
:
MAX
(
|AI1|, |AI2|
)
8
:
MIN
(
|AI1|, |AI2|
)
0
〇
PA-03
PID action direction
0: Positive action 1: Negative
0
〇
PA-04
PID given feedback
range
0
~
65535
1000
〇
PA-05
Proportional gain Kp1
0.0
~
100.0
20.0
〇
PA-06
Integration time Ti1
0.01s
~
10.00s
2.00s
〇
PA-07
Derivative time Td1
0.000s
~
10.000s
0.000s
〇
PA-08
PID reverse cutoff
frequency
0.00
~
Maximum frequency
2.00Hz
〇
PA-09
PID deviation limit
0.0%
~
100.0%
0.0%
〇
PA-10
PID differential limiting
0.00%
~
100.00%
0.10%
〇
PA-11
PID given change time
0.00
~
650.00s
0.00s
〇
PA-12
PID feedback filter time
0.00
~
60.00s
0.00s
〇
PA-13
PID output filtering time
0.00
~
60.00s
0.00s
〇
PA-15
Proportional gain Kp2
0.0
~
100.0
20.0
〇
PA-16
Integration time Ti2
0.01s
~
10.00s
2.00s
〇
PA-17
Derivative time Td2
0.000s
~
10.000s
0.000s
〇
PA-18
PID parameter
switching condition
0: Do not switch
1: Switch through the input terminal
2: Automatic switching according to
deviation
0
〇
PA-19
PID parameter
switching deviation 1
0.0%
~
PA-20
20.0%
〇
PA-20
PID parameter
switching deviation 2
PA-19
~
100.0%
80.0%
〇
PA-21
PID initial value
0.0%
~
100.0%
0.0%
〇
PA-22
PID initial value hold
time
0.00
~
650.00s
0.00s
〇