Chapter 6 P4 input terminal
69
Please note when using a braking resistor or installing a brake unit or using an energy feedback
unit
Please set P3-11 “overexcitation gain” value to “0”. If it is not “0”, it may cause excessive current
during operation. Please set P3-23 “Overvoltage stall enable” value to “0”. If it is not “0”, it may
P4 Group Input terminal
The inverter comes standard with 6 multi-function digital input terminals (X6 can be used as
high-speed pulse input terminal), 2 analog input terminals
。
P4-00
X1 terminal function selection Default: 1 (forward running)
P4-01
X2 terminal function selection Default: 4 (forward jog)
P4-02
X3 terminal function selection Default: 9 (fault reset)
P4-03
X4 terminal function selection Default: 12 (multi-speed 1)
P4-04
X6 terminal function selection Default: 13 (multi-speed 2)
P4-05
X5 terminal function selection
Default
:
0
P4-06
X7 terminal function selection
Default
:
0
P4-07
X8 terminal function selection
Default
:
0
P4-08
X9 terminal function selection
Default
:
0
These parameters are used to set the function of the digital multi-function input
terminal. The functions that can be selected are shown in the table below.
:
Setting
value
Function
Instruction
0
No function
The unused terminals can be set to “No function” to
prevent malfunction.
1
Forward running (X1)
The inverter is controlled to rotate forward and reverse
P3-22
Overvoltage stall operating voltage
200.0V~2000.0V
Default
:
depending
P3-23
Overvoltage stall enable
0 is invalid, 1 is valid
Default
:
0
P3-24
Overvoltage stall suppression
frequency gain
0~100
Default
:
30
P3-25
Overvoltage stall suppression voltage
gain
0~100
Default
:
30
P3-26
Overvoltage stall maximum rising
frequency limit
0~50Hz
Default
:
5Hz
P3-27
Slip compensation time constant
0.1~10.0s
Default
:
0.5
The smaller the response time value of the slip compensation is set, the faster the response
speed is.