78
Chapter 6 P4 input terminal
P4-21
AI curve 2 maximum input
corresponding value
-100.0%
~
+100.0%
Default
:
100.0%
P4-22
AI2 filtering time
0.00s
~
10.00s
Default
:
0.10s
For the function and usage of curve 2, please refer to the description of curve 1.
P4-23
AI curve 3 minimum input
-10.00V
~
P4-25
Default
:
-10.00V
P4-24
AI curve 3 minimum input
corresponding value
-100.0%
~
+100.0%
Default
:
-100.0%
P4-25
AI curve 3 maximum input
P4-23
~
+10.00V
Default
:
10.00V
P4-26
AI curve 3 maximum input
corresponding value
-100.0%
~
+100.0%
Default
:
100.0%
P4-27
AI3 filtering time
0.00s
~
10.00s
Default
:
0.10s
For the function and usage of curve 3, please refer to the description of curve 1.
P4-28
Pulse minimum input
0.00kHz
~
P4-30
Default
:
0.00kHz
P4-29
Pulse minimum input
corresponding value
-100.0%
~
100.0%
Default
:
0.0%
P4-30
Pulse maximum input
P4-28
~
100.00kHz
Default
:
50.00kHz
P4-31
Pulse maximum input
corresponding value
-100.0%
~
100.0%
Default
:
100.0%
P4-32
Pulse input filtering
time
0.00s
~
10.00s
Default
:
0.10s
This group of function codes is used to set the relationship between the multi-function
terminal X6 pulse input frequency and the corresponding setting.
The pulse frequency is only valid at the X6 terminal. The application of this group of
functions is similar to curve 1, please refer to the description of curve 1.
P4-33
AI curve selection
Unit: AI1 curve selection
1: curve 1 (2 points, P4-13 to P4-16)
2: Curve 2 (2 points, P4-18 to P4-21)
3: Curve 3 (2 points, P4-23 to P4-26)
4: Curve 4 (4 points, A6-00 to A6-07)
5: Curve 5 (4 points, A6-08 to A6-15)
Ten: AI2 curve selection, ibid.
Hundreds: AI3 curve selection, ibid.
Default
:
321
The unit’s digit, ten’s digit, and hundred’s digit of the function code are used to select