Chapter 6 P0 group basic function
57
P0-27
Command
source bundle
frequency
source
Single digit: operation panel command binding
frequency source selection
0: No binding 1: Digital setting frequency
2: AI1 3: AI2
4: AI3 5: Pulse X6
6: Multi-speed 7: Simple PLC
8: PID 9: Communication given
Tens: terminal command binding frequency
source selection
Hundreds: Communication command binding
frequency source selection
Thousands: automatic running binding
frequency source selection
Default
:
0000
Define the bundle combination between the three running command channels and the
nine frequency references to facilitate synchronous switching.
The above frequency given channel has the same meaning as the main frequency
source X selects P0-03. Different running command channels can bundle the same
frequency given channel. When the command source has a bundled frequency source,
the frequency source set by P0-03~P0-07 is no longer active during the valid period of
the command source.
P1 Group First motor parameter
P1-00
Motor type selection
0
:
General asynchronous motor 1:
variable frequency asynchronous motor
Default
:
0
P1-01
Motor rated power
0.1kW
~
1000.0kW
depending
P1-02
Motor rated voltage
1V
~
2000V
depending
P1-03
Motor rated current
0.1A
~
6553.5A
depend
P1-04
Motor rated frequency
0.01Hz
~
Maximum frequency
depend
P1-05
Motor rated speed
1rpm
~
65535rpm
depend
The above function code is the motor parameter, and the relevant parameters are
accurately set according to the motor nameplate.
In order to obtain better VF or vector control performance, motor parameter tuning is
required, and the accuracy of the adjustment result is closely related to the correct
setting of the motor nameplate parameters.
P1-06
Asynchronous motor
stator resistance
0.001Ω
~
65.535Ω
Tuning
parameter
P1-07
Asynchronous motor
rotor resistance
0.001Ω
~
65.535Ω
Tuning