Technical Data safe inputs, STO-Inputs and Daisy-Chain-Inputs
Operation Manual
Safety Module for b maXX 5000
BM5-O-SAF-002/3
Document no.: 5.11016.03
Baumüller Nürnberg GmbH
164
C.2
C.2.1
Technical data Daisy-Chain-Outputs
Rated output voltage
24 V
Rated output current
50 mA
Proof voltage
60 V
Output type
protected output according to EN 61131-2
Test pulse length: 800 µs (always active)
C.2.2
Technical data safe outputs
Rated output voltage
24 V
Rated output current
500 mA
Required minimum current
50 mA
Proof voltage
60 V
Output type
protected output according to EN 61131-2.
Test pulse length: 800 µs (always active)
C.2.3
Technical data cycle outputs
Rated output voltage
24 V
Rated output current
50 mA
Output type
protected output according to EN 61131-2.
Test pulse length: 800 µs (active, if at least one input was parameterized as "Sensor type
passive").
C.2.4
Technical data power outputs
Rated output voltage
24 V / 48 V
(for details see Operating Manual b maXX 5000)
Rated output current
4 A
Proof voltage
60 V
Output type
protected output according to EN 61131-2.
Test pulse length: 2800 µs (always active)
Summary of Contents for BM5-O-SAF-002