7-12 Parameter Descriptions
MN765
Block Title Parameter (Number)
Selection (Value)
Parameter Name and Description
MOTOR
CONTROL
(Continued)
CUSTOM V/F CURVE
(1617)
Only available or active in V/F
mode. Ignore this parameter
for Vector modes.
Preset Value: 0
Range: 0 - 2
Off (0) Curve set in parameter “V/F Profile” (P1616).
3 Point (1) Allows two linear V/F segments by setting the V/F 3 Point Volts and V/F 3 Point
Frequency parameters.
7 Point (2) Allows six linear V/F segments by setting the 7-Point voltage and frequency values.
Allows custom V/F Curve profile settings to taylor the V/F Curve to specific
applications for optimum performance. Only available or active when “Control
Type” (P1601) is set to PM V/F Control. Takes precedence over “V/F Profile”
(P1616).
3 PT
Volts
3 Point Method Curve
Control Base Volt
(P1611)
Static
Boost
Output Volts
Base
Freq.
Output Frequency
3 PT Freq.
3 POINT VOLTAGE
(1618)
Only available or active in V/F
mode. Ignore this parameter
for Vector modes.
Preset Value: 0.0
Range: 0.0 - 100.0%
The output voltage associated with the 3 Point Frequency parameter. Calculated as
a percentage of drive rated output voltage.
3 POINT FREQ
(1619)
Only available or active in V/F
mode. Ignore this parameter
for Vector modes.
Preset Value: 30.00
Range: 0.00 - maximum output speed P2003 Hz
The output frequency associated with the 3 Point Volts parameter.
SLIP COMP ENABLE
(1620)
Only available or active in V/F
mode. Ignore this parameter
for Vector modes.
Preset Value: 0
Range: 0 - 1
Off (0) Slip compensating disabled.
On (1) Slip compensating enabled.
Compensates for change in slip due to varying load conditions during normal
operation to maintain constant rotor speed.
7 POINT FREQ 1
(1621)
7 POINT FREQ 2
(1623)
7 POINT FREQ 3
(1625)
7 POINT FREQ 4
(1627)
7 POINT FREQ 5
(1629)
Only available or active in V/F
mode. Ignore this parameter
for vector modes.
Preset Value: 300
Preset Value: 600
Preset Value: 900
Preset Value: 1200
Preset Value: 1500
Range: 0 - Max Speed RPM
Coupled with the 7 Point Voltage parameters to set the frequency portion of the
breakpoints in the 7-point V/F curve.
Table 7-1 Level 1 Parameter Block Definitions Continued
Summary of Contents for VS1GV21-1B
Page 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Page 12: ...2 2 General Information MN765...
Page 16: ...3 4 Installing the Drive MN765...
Page 78: ...6 16 Using the Keypad MN765...
Page 132: ...9 14 Troubleshooting MN765...
Page 172: ...A 16 Technical Specifications MN765...
Page 200: ...E 2 Remote Keypad Mounting Template MN765...
Page 201: ...Remote Keypad Mounting Template E 3 MN765...