4-10 Power Wiring
MN765
Figure 4-8 Single Phase Power Control Connections
L1
L2
L1
L2
N
Earth
*Optional components not provided with control.
Note 3
Baldor
Control
*Optional
Line
Reactor
Note 1
Note 3
A1
B1
A2
B2
Note 4
GND
Note 2
*Fuses
See recommended tightening torques in Table A-2.
240VAC Single Phase
L1
N
L1
L2
N
Earth
Note 3
Baldor
Control
*Optional
Line
Reactor
Note 1
Note 3
A1
A2
Note 4
GND
Note 2
*Fuses
120VAC Single Phase
NOTES:
1. See Table 4-6.
2. Use same gauge wire for Earth ground as is used for L1, L2 and N.
3. Metal conduit should be used. Connect conduits so the use of a reactor or RC Device does not interrupt EMI/RFI
shielding.
4. See Line/Load Reactors described previously in this section.
Table 4-9 Single Phase Rating Wire Size and Protection Devices - 120/240VAC Controls
HP
120VAC Single Phase Input
240VAC Single Phase Input
Input
Amps
Input Fuse (Amps)
Fast Acting
AWG
mm
2
Input
Amps
Input Fuse (Amps)
Fast Acting
AWG
mm
2
1
12
20
12
4.0
6.3
12
14
2.5
2
20
30
10
6.0
10.2
20
14
2.5
3
30
35
10
6.0
14.4
25
12
4.0
Note:
All wire sizes are based on 75
0
C copper wire. Recommended fuses are based on 40
0
C ambient, maximum continuous
control output and no harmonic current.
Summary of Contents for VS1GV21-1B
Page 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Page 12: ...2 2 General Information MN765...
Page 16: ...3 4 Installing the Drive MN765...
Page 78: ...6 16 Using the Keypad MN765...
Page 132: ...9 14 Troubleshooting MN765...
Page 172: ...A 16 Technical Specifications MN765...
Page 200: ...E 2 Remote Keypad Mounting Template MN765...
Page 201: ...Remote Keypad Mounting Template E 3 MN765...