4-6 Power Wiring
MN765
4.8 Incoming Power and Motor Connections
Figure 4-3 shows the layout of the terminals on the power connectors for each size drive. All cables must be in conduits
or shielded and the conduits or shields must be grounded at the cable entrance. The brake resistor and cable must be in a
conduit or shielded if installed outside the enclosure.
Figure 4-3 Power Connections
Frame Size AA 1-Phase Input Drives
Frame Size B and C Drives
GND
TH2
TH1
T3
T2
T1
B-
R2
B+/R1
L3
L2
L1
GND
TH2
TH1
T3
T2
T1
B-
R2
R1/B+
GND
N
L2
L1
Input AC Power
Motor Thermal
Leads
*
Input AC Power
Motor Thermal
Leads
Motor GND
Motor
Chassis
Ground
*
Dynamic Brake
Motor Leads
See recommended tightening torques in Table A-2.
*Remove TH1 to TH2 jumper if Motor Thermal Leads are connected.
Motor Leads
Dynamic Brake
Input AC Power
Dynamic Brake
Motor Leads
Frame Size E Drives
T3
T2
T1
Ground
GND
TH2
TH1
L3
L2
L1
B-
R2
B+/R1
Frame Size AA 3-Phase Input Drives
GND
TH2
TH1
T3
T2
T1
B-
R2
R1/B+
GND
L3
L2
L1
Input AC Power
Motor Thermal
Leads
Motor GND
Motor
Chassis
Ground
*
Dynamic Brake
Motor Leads
Motor Thermal
Leads
*
L3
L2
L1
Ground
GND
TH2
TH1
Motor Thermal
Leads *
Frame Size D Drives
Dynamic Brake
B-
R2
B+/R1
Motor Leads
T3
T2
T1
Note: Thermal lead terminal block mounted
on left side wall.
GND
TH2
TH1
Motor Thermal
Leads *
Motor Leads
T3
T2
T1
R2
R1
Dynamic Brake
L3
L2
L1
Input AC Power
Ground
Input AC Power
Note: An open circuit between TH1 and TH2 will cause an overtemperature fault.
Refer to fault/troubleshooting information in Chapter 9.
Frame Size F Drives
1. Access the Power and Motor Terminals (see Cover Removal procedure).
2. Feed the power supply and motor cables into the drive through the cable entrance.
3. Connect the line L1, L2, L3 and GND to the power terminal connectors, Figure 4-4.
4. Connect motor leads to T1, T2, T3 and GND motor terminal connectors.
Note:
H2E-Frame Size, 250HP and 300HP (575V) drives utilize studs for power terminations.
Summary of Contents for VS1GV21-1B
Page 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Page 12: ...2 2 General Information MN765...
Page 16: ...3 4 Installing the Drive MN765...
Page 78: ...6 16 Using the Keypad MN765...
Page 132: ...9 14 Troubleshooting MN765...
Page 172: ...A 16 Technical Specifications MN765...
Page 200: ...E 2 Remote Keypad Mounting Template MN765...
Page 201: ...Remote Keypad Mounting Template E 3 MN765...