7-30 Parameter Descriptions
MN765
Block Title Parameter (Number)
Selection (Value)
Parameter Name and Description
AUTO
TUNE
(Continued)
CUR. LOOP TUNE
(2906)
Only available or active in Vector
modes. Ignore for V/F mode.
Preset Value: 0
Range: 0 - 1
No (0) No action.
Yes (1) Tunes the current controller loop.
FLUX CUR. TUNE
(2907)
Only available or active in Vector
modes. Ignore for V/F mode.
Preset Value: 0
Range: 0 - 1
No (0) No action.
Yes (1) Tunes the flux controller loop. This is a rotational test.
FEEDBACK TEST
(2908)
Only available or active in Vector
modes. Ignore for V/F mode.
Preset Value: 0
Range: 0 - 1
No (0) No action.
Yes (1) Checks and adjusts for feedback alignment. This is a rotational test.
SLIP FREQ TUNE
(2909)
Only available or active in Vector
modes. Ignore for V/F mode.
Preset Value: 0
Range: 0 - 1
No (0) No action.
Yes (1) Tunes slip frequency. This is a calculation based upon the most recent motor
parameter settings (non-rotational).
SPEED LOOP TUNE
(2910)
Only available or active in Vector
modes. Ignore for V/F mode.
Preset Value: 0
Range: 0 - 1
No (0) No action.
Yes (1) Tunes the speed controller loop. This is a rotational test.
Table 7-2 Level 2 Parameter Block Definitions Continued
Summary of Contents for VS1GV21-1B
Page 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Page 12: ...2 2 General Information MN765...
Page 16: ...3 4 Installing the Drive MN765...
Page 78: ...6 16 Using the Keypad MN765...
Page 132: ...9 14 Troubleshooting MN765...
Page 172: ...A 16 Technical Specifications MN765...
Page 200: ...E 2 Remote Keypad Mounting Template MN765...
Page 201: ...Remote Keypad Mounting Template E 3 MN765...