7-26 Parameter Descriptions
MN765
Block Title Parameter (Number)
Selection (Value)
Parameter Name and Description
PROCESS
CONTROL
PROCESS TYPE
(2601)
Preset Value: 0
Range: 0 - 2
None (0) PID is disabled, however feedforward is always available.
Forward Acting (1) The process error computed as: PE = (Set Point) - (Feedback). Useful when
feedback increases as motor speed increases.
Reverse Acting (2) The process error computed as: PE =(Feedback) - (Set Point). Useful when
feedback decreases as motor speed increases.
Sets the type of PID control.
SETPOINT ADJ LIM
(2602)
Preset Value: 10.0
Range: 0.0 - 100.0%
Set as a percent of motor speed. It limits speed corrections due to process
error.
PROC FEEDBACK
(2603)
Preset Value: 0
Range: 0 - 10
None (0) No feedback assigned.
Setpoint Cmd (1) Setpoint command value used for feedback.
Loc Speed Ref (2) Local speed reference used for feedback.
Analog In1 (3) Analog Input 1 signal used for feedback.
Analog In2 (4) Analog Input 2 signal used for feedback.
Network (5) Network value used for feedback.
Composite Ref (6) Output of Composite Ref signal used for feedback.
Opt1 Ana In1 (7) Option 1, Analog Input 1 used for feedback.
Opt1 Ana In2 (8) Option 1, Analog Input 2 used for feedback.
Opt2 Ana In1 (9) Option 2, Analog Input 1 used for feedback.
Opt2 Ana In2 (10) Option 2, Analog Input 2 used for feedback.
Sets the type of signal used for the process feedback signal.
SETPOINT SOURCE
(2604)
Preset Value: 0
Range: 0 - 10
None (0) Source of Process Loop Setpoint is not defined.
Setpoint Cmd (1) Setpoint command value used for Setpoint.
Loc Speed Ref (2) Local speed reference used for Setpoint.
Analog In1 (3) Analog Input 1 signal used for Setpoint.
Analog In2 (4) Analog Input 2 signal used for Setpoint.
Network (5) Network value used for Setpoint.
Composite Ref (6) Output of Composite Ref signal used for Setpoint.
Opt1 Ana In1 (7) Option 1, Analog Input 1 used for Setpoint.
Opt1 Ana In2 (8) Option 1, Analog Input 2 used for Setpoint.
Opt2 Ana In1 (9) Option 2, Analog Input 1 used for Setpoint.
Opt2 Ana In2 (10) Option 2, Analog Input 2 used for Setpoint.
Sets the source input signal type to which the process feedback will be
compared. If “Setpoint CMD” is selected, the fixed value of the set point is
entered in the Setpoint Command parameter value.
SETPOINT COMMAND
(2605)
Preset Value: 0.0
Range: -100.0% to +100.0%
Sets the value as a percentage of the process feedback signal; the control will
try to maintain by adjusting motor speed. This is only used when the Setpoint
Source is a fixed value “Setpoint CMD” under Setpoint Source.
Table 7-2 Level 2 Parameter Block Definitions Continued
Summary of Contents for VS1GV21-1B
Page 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Page 12: ...2 2 General Information MN765...
Page 16: ...3 4 Installing the Drive MN765...
Page 78: ...6 16 Using the Keypad MN765...
Page 132: ...9 14 Troubleshooting MN765...
Page 172: ...A 16 Technical Specifications MN765...
Page 200: ...E 2 Remote Keypad Mounting Template MN765...
Page 201: ...Remote Keypad Mounting Template E 3 MN765...