Troubleshooting 9-9
MN765
Keypad Text
Type
Fault
Number
Description
Dyn Brake Desat
Fault
36
Dynamic braking current limit exceeded. Check for shorted braking resistor
circuit or for brake resistor with an ohmic value below the allowed limit for the
drive. Check for a short between R1 or R2 and B-.
Encoder Loss
Fault
58
Encoder detected but has poor or no signal. Check encoder wiring; verify
shielding, grounding and bonding practices.
Excess Faults/Hr
Alarm
79
The allowed number of faults/hour has been exceeded.
External Trip
Fault
22
J1-16 is open. Check remote connection on J1-16. Occurs only when external
fault parameter is turned ON.
Fan Loss
Alarm
62
Fan circuit is seeing low current or over current. Verify that fan is not blocked
and is connected properly.
Flt Log Mem Fail
Fault
28
Problem reading fault log from control board EEPROM, contact Baldor for
service.
Following Error
Fault
18
Speed error beyond Set Speed Band parameter. Verify motor is not overloaded;
increase Set Speed Band.
Ground Fault
Fault
8
Ground currents in output of control. Due to shorts to ground or excessive
leakage current to ground. Disconnect motor, meg motor for insulation leakage
to ground; check motor leads for shorts to ground; replace motor leads with
lower capacitance cable or shorten leads if possible; consider the usage of load
reactor.
High Line
Alarm
102
Power grid voltage too high, check power base rating, check input lines.
IGBT Thermal
Fault
94
IGBT thermal overload. Check motor loading. Allow time to cool.
Initial Pos
Alarm
70
The initial position reading could not be read or is out of expected range. Check
motor feedback wiring. Verify proper wiring, grounding and bonding.
Internal Config
Fault
35
An internal firmware configuration occurred, contact Baldor for service.
Invalid FB Sel
Alarm
56
Feedback board not installed in selected slot. Select an Encoder/Resolver
board as feedback source. Verify selection of correct slot for motor feedback.
Invalid Res Sel
Alarm
71
The feedback source selected is not a resolver board. If resolver feedback
utilized, ensure installed feedback board is for resolver feedback. Verify
selection of correct slot for motor feedback.
Line Loss
Alarm
37
All 3 input phases lost. Check input circuit breaker, fuses or input contacts
Line Regen
Fault
34
This fault code is not used. If it occurs, contact Baldor for service
Line Sag
Alarm
64
All 3 phase input lines have sagged below 70% of nominal. Check input line
quality; check line impedance; check for excessive loading on power system.
Logic Supply
Fault
9
Internal logic power supply has dropped below 24V threshold. Replace Power
Supply.
Low Initial Bus
Fault
11
Bus volt below 200/400/500V on 230/460/575V units at power up. Check input
line voltage; check for proper resistor on R1/R2; check for open circuit on TH1-
TH2 Terminals.
Low Line
Alarm
101
Power grid voltage too low. Check power base rating; check input connections;
ensure input voltage is within drive specification.
Lower U Gate
Fault
40
Transistor #1 failed to fire or misfired. Verify IGBT is not shorted. Verify no
debris has fallen into drive. Check wiring between drive and motor. Verify motor
windings are not shorted.
Lower V Gate
Fault
42
Transistor #2 failed to fire or misfired. Verify IGBT is not shorted. Verify no
debris has fallen into drive. Check wiring between drive and motor. Verify motor
windings are not shorted.
Lower W Gate
Fault
44
Transistor #3 failed to fire or misfired. Verify IGBT is not shorted. Verify no
debris has fallen into drive. Check wiring between drive and motor. Verify motor
windings are not shorted.
Macro Cmd Failed
Fault
93
Macro command execution failure. Verify that macro file is correct.
Macro Cmd Inval
Fault
92
Macro command found is invalid. Verify that macro file is correct.
Macro Read
Fault
90
Macro record read failed. Recompile file and download to drive again.
Macro Rec Length
Fault
91
Macro record length is invalid. Recompile file and download to drive again.
Table 9-1
Fault Messages
Continued
Summary of Contents for VS1GV21-1B
Page 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Page 12: ...2 2 General Information MN765...
Page 16: ...3 4 Installing the Drive MN765...
Page 78: ...6 16 Using the Keypad MN765...
Page 132: ...9 14 Troubleshooting MN765...
Page 172: ...A 16 Technical Specifications MN765...
Page 200: ...E 2 Remote Keypad Mounting Template MN765...
Page 201: ...Remote Keypad Mounting Template E 3 MN765...