Appendix E. CE Mark compliance
E.1 Introduction
For CE Mark compliance, the PanaFlow™ LC flow meter must be wired in accordance with the instructions in this appendix.
IMPORTANT:
CE Mark compliance is required for all units intended for use in EU countries.
E.2 Wiring
The PanaFlow™ LC must be wired with the recommended cable, and all connections must be properly shielded and
grounded. Refer to Table 33 below for the specific requirements.
Table 33: Wiring Requirements
Connection
Cable Type
Ground Termination
Transducer
Armored RG62 A/U
Grounded using a cable gland.
Input/Output
Armored 22 AWG shielded (e.g.
Baystate #78-1197) with armored
material added to outside of jacket
Grounded using a cable gland.
Power
Armored 14 AWG 3 conductor
Grounded using a cable gland.
Note:
If the PanaFlow™ LC is wired as described in this appendix, the unit will comply with the EMC Directive.
93
Summary of Contents for Panametrics PanaFlow LC
Page 1: ...PanaFlow LC User s manual 910 327 Rev A...
Page 2: ...ii...
Page 3: ...PanaFlow LC Panametrics liquid ultrasonic flowmeter User s manual 910 327 Rev A Sep 2019 iii...
Page 4: ...no content intended for this page iv...
Page 12: ...no content intended for this page xii...
Page 44: ...Figure 58 Setting up pulse output 32...
Page 49: ...Figure 60 Setting up alarm output 37...
Page 80: ...no content intended for this page 68...
Page 82: ...no content intended for this page 70...
Page 86: ...no content intended for this page 74...
Page 98: ...Table 30 Service Record Date Description of Service Performed By 86...
Page 104: ...no content intended for this page 92...
Page 106: ...no content intended for this page 94...
Page 114: ...no content intended for this page 102...
Page 138: ...no content intended for this page 126...
Page 140: ...no content intended for this page 128...