Table. 5.4.5 - 72. Measurement inputs of the I0dir> function.
Signal
Description
Time base
I01RMS
RMS measurement of coarse residual current measurement input I01
5ms
I01TRMS
TRMS measurement of coarse residual current measurement input I01
5ms
I01PP
Peak-to-peak measurement of coarse residual current measurement input I01
5ms
I02RMS
RMS measurement of sensitive residual current measurement input I02
5ms
I02TRMS
TRMS measurement of coarse sensitive current measurement input I02
5ms
I02PP
Peak-to-peak measurement of sensitive residual current measurement input I02
5ms
I0Calc
RMS value of the calculated residual current from the three phase currents
5ms
U0RMS
RMS measurement of zero sequence voltage measurement input U0
5ms
U0Calc
RMS value of the calculated zero sequence voltage from the three phase voltages
5ms
The selection of the used AI channel is made with a setting parameter. In all possible input channel
variations the pre-fault condition is presented with a 20 ms averaged history value from -20 ms from
a START or TRIP event.
General settings
The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.4.5 - 73. General settings of the function.
Name
Range
Default
Description
I0dir> LN
mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
1: On
Set mode of DEF block.
This parameter is visible only when
Allow setting of individual LN mode is enabled in
General menu.
U0
directional
phase
1: U0
2: -U0
1: U0
If the connected neutral voltage polarity is opposite to the connected residual current,
this parameter can swap the angle reference.
U0> Meas
input select
1: Select
2: U0
Calculated
3: U3
Input
4: U4
Input
1:
Select
Defines which available neutral voltage measurement is used. Available neutral
voltages depend on measurement settings (
Measurements
→
Transformers
→
VT
module).
Measured
magnitude
1: RMS
2: TRMS
3: Peak-
to-peak
1: RMS
Defines which available measured magnitude is used by the function. This parameter
is available when "Input selection" has been set to "I01" or "I02".
Measurement
side
1: Side 1
2: Side 2
1: Side
1
Defines which current measurement module is used by the function.
Input
selection
1: I01
2: I02
3: I0Calc
1: I01
Defines which measured residual current is used by the function.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
85