Figure. 6.2.1.3.2 - 215. FCR transfer function.
The FCR control mode is activated by the operator or by the voltage supervision function (
Excitation
→
Supervision
→
"Voltage supervision"), and it is deactivated when the user selects another control
mode. The reference value can be adjusted locally and remotely.
Table. 6.2.1.3.2 - 358. FCR control mode setting parameters.
Name
Range
Step
Default
Description
FCR control
status
0: FCR mode ON
1: Increase reference ON
2: Decrease reference
ON
3: Start reference ON
4: Increase inhibit ON
5: Decrease inhibit ON
6: Reference on high limit
7: Reference on low limit
8: Reference on tracking
now
9: Starting finished
10: Bus reference ON
11: Electrical brake ON
-
-
Displays the status of the field current regulator.
FCR
reference
now
-500.00…500.00p.u./p.u. 0.01p.u./p.u. -
Displays the FCR reference value at the moment.
Minimum
FCR
reference
allowed
-500.00…500.00p.u./p.u. 0.01p.u./p.u. -
Displays the minimum allowed value of the FCR
reference.
Maximum
FCR
reference
allowed
-500.00…500.00p.u./p.u. 0.01p.u./p.u. -
Displays the maximum allowed value of the FCR
reference.
FCR
proportional
gain KpFCR
(field
voltage/field
current)
0.00…50.00p.u/p.u
0.01p.u/p.u
5.00p.u/
p.u
Defines the proportional gain for the FCR.
Integral gain
KiFCR
0.00…10.00 1/s
0.01 1/s
0.20 1/s
Defines the integral gain for the FCR.
FCR
reference on
start
0.00…2.00p.u.
0.01p.u.
1.00p.u.
Defines the start-up reference value for the
generator.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
434
© Arcteq Relays Ltd
IM00001