Signals
Description
tanfi3PH
tanfiL1
tanfiL2
tanfiL3
Tan (φ) of three-phase powers and phase powers.
cosfi3PH
cosfiL1
cosfiL2
cosfiL3
Cos (φ) of three-phase powers and phase powers.
Impedances and admittances
RL12, RL23, RL31
XL12, XL23, XL31
RL1, RL2, RL3
XL1, XL2, XL3
Z12, Z23, Z31
ZL1, ZL2, ZL3
Phase-to-phase and phase-to-neutral resistances, reactances and impedances.
Z12Ang, Z23Ang, Z31Ang,
ZL1Ang, ZL2Ang, ZL3Ang
Phase-to-phase and phase-to-neutral impedance angles.
Rseq, Xseq, Zseq
RseqAng, XseqAng, ZseqAng
Positive sequence resistance, reactance and impedance values and angles.
GL1, GL2, GL3, G0
BL1, BL2, BL3, B0
YL1, YL2, YL3, Y0
Conductances, susceptances and admittances.
YL1angle, YL2angle, YL3angle,
Y0angle
Admittance angles.
Others
System f.
Used tracking frequency at the moment.
Ref f1
Reference frequency 1.
Ref f2
Reference frequency 2.
M thermal T
Motor thermal temperature.
F thermal T
Feeder thermal temperature.
T thermal T
Transformer thermal temperature.
RTD meas 1…16
RTD measurement channels 1…16.
Ext RTD meas 1…8
External RTD measurement channels 1…8 (ADAM module).
Settings
Table. 7.3 - 407. Settings.
Name
Range
Step Default
Description
Measurement value
recorder mode
0: Disabled
1: Activated
-
0:
Disabled
Activates and disables the real-time signals to
communication.
Scale current
values to primary
0: No
1: Yes
-
0: No
Selects whether or not values are scaled to
primary.
Slot X magnitude
selection
0: Currents
1: Voltages
2: Powers
3: Impedance (ZRX) and
admittance (YGB)
4: Others
-
0:
Currents
Selects the measured magnitude catecory of the
chosen slot.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
485
Summary of Contents for Generator Commander
Page 1: ...Generator Commander Instruction manual...
Page 2: ......