Name
Range
Step Default
Description
Local integrator status
–3000.000…3000.000 0.001 -
Displays the active mode integrator part of the
selected channel.
This setting is only visible when the "Commanders in
use" parameter is set to "Redundant".
Select remote integrator
status input
0: GOOSE input 1
...
19: GOOSE input 20
-
0:
GOOSE
input 1
Selects the GOOSE input which is used to receive
the active mode integrator part from another
channel.
This setting is only visible when the "Commanders in
use" parameter is set to "Redundant".
Remote integrator status
–3000.000…3000.000 0.001 -
Displays the received value of the active integrator
part of another channel.
This setting is only visible when the "Commanders in
use" parameter is set to "Redundant".
Local excitation current
measurement
–3000.000…3000.000 0.001 -
Displays the excitation current measurement of the
selected channel.
This setting is only visible when the "Commanders in
use" parameter is set to "Redundant".
Select remote excitation
current measurement
input
0: GOOSE input 1
...
19: GOOSE input 20
-
0:
GOOSE
input 1
Selects the GOOSE input for the excitation current
measurement from another channel.
This setting is only visible when the "Commanders in
use" parameter is set to "Redundant".
Remote excitation current
measurement
–3000.000…3000.000 0.001 -
Displays the excitation current measurement from
another channel.
This setting is only visible when the "Commanders in
use" parameter is set to "Redundant".
Table. 6.2.2.5 - 376. Redundancy configuration.
Redundant bridges configuration
Name
Description
Select channel (0=A
1=B)
Selects the digital input from the auxiliary relay which is connected via an active ChA. ChB selects
both ChA (NC) and ChB (NO).
R
Red
edundant contr
undant control config
ol configura
uration
tion
Name
Name
Descrip
Description
tion
Disable commands to
bridge
Selects the signal which disables all commands to the redundant bridge.
Local channel status
Displays the status of the local channel; by default "Always true".
Remote channel
status
Displays the status of the remote channel; by default "Always true".
Table. 6.2.2.5 - 377. Active bridge input status (DI and AI).
Name
Range
Step
Default
Description
Active bridge
DIx
0: Off
1: On
-
0: Off
Indicates whether a specific digital input (1…8) is ON or OFF.
Active bridge
mA input value
0.000…20.000mA 0.001mA -
Displays the current measurement value of the active bridge.
Active bridge U
input value
0.000…10.000V
0.001V
-
Displays the U input measurement value of the active bridge.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
455