10.1.3.8 Double ST 100 Mbps Ethernet communication module
Table. 10.1.3.8 - 440. Technical data for the double ST 100 Mbps Ethernet communication module.
General information
Ports
ST connectors (2) and IRIG-B connector (1)
Protocols
Protocols
IEC61850, DNP/TCP, Modbus/TCP, IEC104 & FTP
ST connectors
Connector type
Duplex ST connectors
62.5/125 μm or 50/125 μm multimode fiber
100BASE-FX
Transmitter wavelength
1260…1360 nm (nominal: 1310 nm)
Receiver wavelength
1100…1600 nm
Maximum distance
2 km
IRIG-B Connector
Connector type
Phoenix Contact MC 1,5/ 2-ST-3,5 BD:1-2
10.1.4 Display
Table. 10.1.4 - 441. Technical data for the HMI TFT display.
Dimensions and resolution
Number of dots/resolution
800 x 480
Size
154.08 × 85.92 mm (6.06 × 3.38 in)
Display
Type of display
TFT
Color
RGB color
10.2 Functions
10.2.1 Protection functions
10.2.1.1 Non-directional overcurrent protection (I>; 50/51)
Table. 10.2.1.1 - 442. Technical data for the non-directional overcurrent function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
RMS phase currents
TRMS phase currents
Peak-to-peak phase currents
Pick-up
Pick-up current setting
0.10…50.00 × I
n
, setting step 0.01 × I
n
Inrush 2nd harmonic blocking
0.10…50.00 %I
fund
, setting step 0.01 %I
fund
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
530
© Arcteq Relays Ltd
IM00001