• operating mode selections
• setting parameters
• digital inputs and logic signals
• measured and pre-processed voltage magnitudes.
The function's output signals can be used for direct I/O controlling and user logic programming. The
time stamp resolution is 1 ms.
Measured input
The function block uses analog voltage measurement values. The monitored magnitude is equal to
RMS values.
Table. 5.5.7 - 270. Measurement inputs of the synchronizer function.
Signal
Description
Time base
U
1
RMS
RMS measurement of voltage U
1
/V
5ms
U
2
RMS
RMS measurement of voltage U
2
/V
5ms
U
3
RMS
RMS measurement of voltage U
3
/V
5ms
U
4
RMS
RMS measurement of voltage U
4
/V
5ms
Setting parameters
Table. 5.5.7 - 271. General setting parameters.
Name
Range
Step
Default
Voltage difference calculation mode
0: System is reference
1: U3/U4 input is reference
-
0: System is reference
Synchronizer voltage reference
0: UL12
1: UL23
2: UL31
3: UL1
4: UL2
5: UL3
-
0: UL12
Synchronizer measurement settings
0: Meas.Conf.Incorrect
1: PP and PE voltages
2: PP Voltages
-
-
Synchronizer status
0: Conf.Error
1: Idle Ready
2: Synchronizing
3: Blocked
-
-
Synchroswitch status
0: Standstill
1: Departing
2: Enclosing
-
-
Magnitude difference
-200.000...200.000%Un
0.001%Un
0%Un
Frequency difference
-100.000...100.000Hz
0.001Hz
0Hz
Angle difference
-360.000...360.000deg
0.001deg
0deg
Magnitude difference on closing BRK
-200.000...200.000%Un
0.001%Un
0%Un
Frequency difference on closing BRK
-100.000...100.000Hz
0.001Hz
0Hz
Angle difference on closing BRK
-360.000...360.000deg
0.001deg
0deg
Estimated BRK Closing time
0.000...360.000s
0.005s
0s
Networks rotating time
0.000...360.000s
0.005s
0s
Genera