Figure. 5.4.17 - 97. Comparing dual time constant thermal replica tripping curves to given motor thermal characteristics.
As the figures above have shown, with estimated time constants from the motor thermal limit
curves the single time constant model underprotects the motor in the stall condition when the motor is
cold. When the motor is hot the model overprotects with a heavy hand, allowing the motor only 30.5
seconds of stalling time of the approximately 67 seconds the motor can withstand. When dual time
constants and dynamic time constants are in use, the relay automatically selects the correct tripping
curves for the thermal replica according to the settings, producing therefore an exact thermal image
response (as compared to the single time constant thermal image). In overload conditions the
response from both of the thermal replicas is acceptable as even a small overshoot is noticed when the
motor is hot. In the curve simulations the hot condition was defined as 70 % of the thermal capacity.
The following figures present the tripping and cooling curves of the thermal replica.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
191