Name
Range
Step
Default
Description
Commands
to rectifier
bridge(s)
0: Disabled
1: Enabled
-
0: Disabled
Indicates whether the Generator commander is connected to or
disconnected from the rectifier bridge(s).
VLAN-
PRIORITY
(Commander
to bridge)
0…7
1
4
Defines the virtual LAN priority channel for communication with the
AQ-GC30 rectifier unit.
VLAN-ID
(Commander
to bridge)
0×0…0×FFF
0×1
0×0 or 0×FFF
(single
system)
0×1
(2-channel
system,
Channel 1)
0×2
(2-channel
system,
Channel 2)
Defines the virtual LAN ID address for communication with the AQ-
GC30 rectifier unit.
Excitation
current
measurement
from
0: CT1 (3ph
HV)
1: CT2 (3ph
LV)
-
1: CT2 (3ph
LV)
Selects the machine current measurement source.
With "CT1 (3ph HV)" the excitation current is measured from Side 1
(e.g. the machine supply side, or the block transformer' HV side).
With "CT2 (3ph LV)" the excitation current is measured from Side 2
(e.g. the machine's star point side).
Power
measurement
currents from
1: CT1
2: CT2
2: CT3
-
1: CT1
Selects which channel is used to measure the relay powers. This
value is used for the entire Generator commander.
CT1 measures powers from Side 1 (e.g. the machine supply side, or
the block transformer's HV side. CT2 measures powers from Side 2
(e.g. the machine's star point side). Option "CT3" can be used when
the device has three (3) current measurement cards.
Full or single-
phase
current
measurement
0: Three-
phase current
measurement
1: Single-
phase current
measurement
-
0: Three-
phase
current
measurement
Selects whether the powers are measured from a single-phase
current or from a three-phase current. This value is used for the
entire Generator Commander.
When the "Single-phase current measurement" option is selected,
you can use the "Single-phase current measured from" parameter to
define the specific phase for the measuring.
Single-phase
current
measured
from
0: All phases
1: IL1 CT
2: IL2 CT
3: IL3 CT
4: I01 CT IL1
5: I01 CT IL2
6: I01 CT IL3
7: I02 CT IL1
8: I02 CT IL2
9: I02 CT IL3
-
0: All phases
If "Single-phase current measurement" was selected for the "Full or
single-phase current measurement" parameter, this parameter is
used to select the specific channel from which the powers are
measured from.
If "All phases" is selected, the powers are measured from IL1, IL2 and
IL3.
If "ILx CT" is selected, the powers are measured from that phase
channel, from the side defined with the "Excitation current
measurement from" parameter.
If "I0x CT ILx" is selected, the powers are measured from the I0x
channel, from the side defined with the "Excitation current
measurement from" parameter. ILx refers to the phase current (Lx)
that is connected to this channel.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
423