• ... the 1st route is enabled, voltages are synchronized, there is no overcurrent ("Negative
sequence measuring voltage"/"Positive sequence measuring voltage" > "Voltage high ratio";
"Positive sequence measuring voltage" > 0.1 p.u.; "Negative sequence phase
current"/"Positive sequence phase current" < "Current low ratio" or "Positive sequence phase
current" < 0.1 p.u.) and supervision is enabled.
• ...the 2nd route, excitation start ("Positive sequence measuring voltage" < 0.1 p.u. and "Field
current actual value" > "Field current level") and supervision are enabled.
• ...the 3rd route, differential supervision ("Positive sequence measuring voltage" – "Supply
voltage actual value" < –0.2 p.u.) and supervision are enabled and the generator is on the
grid.
Table. 6.2.1.2 - 356. Voltage supervision settings.
Name
Range
Step
Default
General
Voltage
supervision
0: Disabled
1: Enabled
-
Enabled
Enables and disables the voltage supervision.
Time delay
0.000…10.0s
0.005s
0.200s
Defines the trip time delay; that is, when either a low
measuring voltage or a low supply voltage signal starts.
Voltage high
ratio
0.000…10.0
0.005
0.3
Defines the ratio between the negative and positive
sequence voltages.
Current low
ratio
0.000…10.0
0.005
0.3
Defines the ratio between the negative and positive
phase currents.
Field current
level
0.000…10.0
0.005
1.0
Defines the triggering level for the field current.
GEN voltage
(U1)
-500.00…500.00p.u./p.u. 0.01p.u.
0.00p.u.
Displays the generator voltage U1.
GEN voltage
(U2)
-500.00…500.00p.u./p.u. 0.01p.u.
0.00p.u.
Displays the generator voltage U2.
Supply
voltage
-500.00…500.00p.u./p.u. 0.01p.u.
0.00p.u.
Displays the supply voltage.
Field
overcurrent
Field
overcurrent
protection
0: Disabled
1: Enabled
-
0:
Disabled
Enables and disables the field overcurrent protection.
The field overcurrent detection is achieved through
comparison: when the control signal value is lower than
the "Shorted IGBT low level detection threshold"
parameter, field overcurrent is detected. Note that the
instant field current limiter must be active.
Shorted IGBT
low level
detection
threshold
0.00…25.00
0.01
1.00
Determines the comparison level for the control
signal when the IGBT is shorted. The control signal
reaches the low value when it keeps the field current at
the instant field current limit.
Detection
time delay
0.000…10.000s
0.005s
3.000s
Determines the trip time for the field overcurrent
protection.
Open field
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
429