The
Pick-up setting U03h< set setting parameter controls the pick-up of the 100 % stator earth fault
protection function. This defines the minimum allowed measured neutral 3
rd
harmonic voltage before
action from the function. The function constantly calculates the ratio between the
U
set
< and the
measured magnitude. The reset ratio of 103 % is built into the function and is always relative to the
U
set
< value.
Table. 5.4.20 - 184. Pick-up settings.
Name
Description
Range
Step
Default
U
0 3rd
meas
input select
Voltage input must be selected if both U3 and U4 have been set to
"U0" mode.
0: U3 input
1: U4 input
2: Select
-
2:
Select
Uset<
Pick-up setting
1.00…100.00%U
n
0.01%U
n
20%U
n
I1< block
If the measured positive sequence current is below this
value, tripping is not allowed. 0 x
I
n
setting disables block.
0.00…100.00xI
n
0.01xI
n
0%U
n
The pick-up activation of the function is not directly equal to the START or TRIP signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.4.20 - 185. Information displayed by the function.
Name
Range
Step
Description
U
0 3rd
< LN
behaviour
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
-
Displays the mode of SEF block.
This parameter is visible only when
Allow setting of individual LN
mode is enabled in General menu.
U
0
3rd
< condition
0: Normal
1: Start
2: Trip
3: Blocked
-
Displays the status of the protection function.
U
0
3rd
< measuring
now
0: No U0 avail!
1: U3 input
2: U4 input
-
Displays used voltage measurement channel. If both U3 and U4
channels have been set to "U0" mode the used input channel must
be selected with "U
03rd
< meas input select" parameter.
U
03rd
< pick-up
setting
0.0...1 000 000V
0.1V
Displays the pick-up setting currently used in volts.
Expected
operating time
0.000...1800.000s
0.005s
Displays the expected operating time when a fault occurs.
Time
remaining to
trip
-1800.000...1800.000s 0.005s
When the function has detected a fault and counts down time
towards a trip, this displays how much time is left before tripping
occurs.
U
meas
/U
set
0.00...1250.00U
m
/U
set
0.01U
m
/U
set
The ratio between the measured third harmonic residual voltage
and the pick-up value.
Measured U
0
3rd
harm (%)
0.00...1250.00%U
0n
0.01%U
0n
Measured third harmonic residual voltage in relation to voltage
transformer nominal.
Measured U
0
3rd
harm (Pri)
0.00...1250.00V
0.01V
Measured third harmonic residual voltage on the primary side of
voltage transformer.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
220
© Arcteq Relays Ltd
IM00001