6.2.2.5 Active control status
NO
NOTE!
TE!
Please note that in all the tables below "A" refers to a local bridge and "B" to a remote
bridge. This also applies to the parameter names and menu/submenu/tab names in the
AQtivate configuration and setting tool.
Table. 6.2.2.5 - 374. Bridge devices monitor.
Name
Range
Step Default
Description
Number of rectifiers
0: Single
1:
Redundant
(1+1)
2:
Redundant
(n–1)
-
0: Single
Selects the excitation system configuration.
Bridge 2 start-up health
check time
0…1800s
1s
30s
Defines the running time at the start before changing to another
channel.
This setting is only visible when the "Number of rectifiers"
parameters is no
nott set to "Single".
Bridge A health status
0: System
OK
1: Failing
-
0:
System
OK
Indicates that the health status of the local (A) bridge is OK.
Bridge B health status
0: System
OK
1: Failing
-
0:
System
OK
Indicates that the health status of the remote (B) bridge is OK.
Active bridge now
0: A
1: B
-
0: A
Indicates which rectifier bridge is currently active.
This setting is only visible when the "Number of rectifiers"
parameters is no
nott set to "Single".
Bridge A DO3
0: Off
1: On
-
0: Off
Forces the digital output 3 (DO3) of the local (A) bridge to be
ON or OFF.
Bridge A DO4
0: Off
1: On
-
0: Off
Forces the digital output 4 (DO4) of the local (A) bridge to
be ON or OFF.
Table. 6.2.2.5 - 375. Local control status ("Control devices monitor").
Name
Range
Step Default
Description
Commanders in use
1: Only this
2: Redundant
-
1: Only
this
Selects the running status of the excitation
configuration for (for example) maintenance
purposes.
This commander is by
default
0: On-line
1: Standby
-
0: On-
line
Selects between the online and the standby channel.
This setting is only visible when the "Commanders in
use" parameter is set to "Redundant".
This commander
controlling mode now
0: On-line
1: Standby
-
-
Indicates the status of the controlling mode.
This setting is only visible when the "Commanders in
use" parameter is set to "Redundant".
Remote commander
status
0: Failing
1: OK
-
-
Indicates the commander status.
This setting is only visible when the "Commanders in
use" parameter is set to "Redundant".
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
454
© Arcteq Relays Ltd
IM00001