Name
Range
Step
Default
Description
Reset
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the user can reset the
excitation settings remotely.
AVR
ref execute
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the AVR reference can be
executed remotely.
AVR
ref value
(remote)
0...450 000V
1V
0V
Sets the AVR reference value remotely.
FCR ref
execute
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the FCR reference can be
executed remotely.
FCR ref
value
(remote)
0.00...100.00A (DC)
0.01A (DC)
0A
(DC)
Sets the FCR reference value remotely.
MVar ref
execute
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the MVar reference can be
executed remotely.
Read MVar
ref from
0: Value from comm bus
1: Value from AI
-
0: Value
from
comm
bus
Selects the source from where the MVar reference
is read, from the remote bus or from the
analog channel.
MVar ref
selection
0: Scaled input 1
1: Scaled input 2
2: Scaled input 3
3: Scaled input 4
-
0:
Scaled
input 1
Selects the analog channel from where the MVar
reference is read.
This setting is only visible when "Value from AI" is
the selected for the "Read MVar ref from"
parameter.
Update
MVar ref
automatically
when
threshold
exceeds
0: No
1: Yes
-
0: No
Selects whether or not the MVar reference is
updated from the AI channel when the threshold
value is exceeded.
This setting is only visible when "Value from AI" is
the selected for the "Read MVar ref from"
parameter.
MVar ref
change
threshold
(AI)
0.000…50.000%
0.001%
0.200%
This hysteresis parameter defines the threshold that
must be exceeded for the reference to be updated
from the selected AI channel.
This setting is only visible when "Yes" is the selected
for the "Update MVar ref automatically when
threshold exceeds" parameter.
MVar ref
value
(remote)
–1000.0000...1000.0000MVar 0.0001MVar 0MVar
Sets the MVar reference value remotely.
PF ref
execute
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the PF reference can be
executed remotely.
PF ref value
(remote)
–1.00...1.00
0.01
0
Sets the PF reference value remotely.
Open FB
command
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the field breaker can be
given an "Open" command remotely.
Close FB
command
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the field breaker can be
given a "Closed" command remotely.
AVR speed
90 (remote)
0: Off
1: On
-
0: Off
Selects whether or not the user can remotely set
the generator to 90 % of its nominal speed, thus
allowing for magnetization to begin.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
457