Name
Range
Step
Default
Description
Test max time
0.00…1800.00s
0.01s
300.00s
Defines the maximum time for the step test. When this
time has elapsed, the step test is automatically disabled.
Step test time left
-
-
-
Indicates the remaining time for the step test.
Step test output
now
–5.000…5.000p.u. 0.001p.u. 0.000p.u. Indicates the current test step effect to the reference
value.
Test waveform
0: Square
1: Sinusoidal
("Sinus")
-
Selects the waveform used in the step test.
Test square
amplitude
–5.000…5.000
0.001
0.000
Defines the amplitude for the square test steps,
when "Square" is the selected test waveform.
Test square duration 0.000...300.000s
0.005s
10.000s
Defines the duration for the square test steps,
when "Square" is the selected test waveform.
Test
sinusoidal frequency 0.00...25.00Hz
0.01Hz
0.00Hz
Defines the frequency for the sinusoidal waves,
when "Sinusoidal" ("Sinus") is the selected test waveform.
Test
sinusoidal amplitude 0.00...25.00p.u.
0.01p.u.
0.00p.u.
Defines the amplitude for the sinusoidal waves,
when "Sinusoidal" ("Sinus") is the selected test waveform.
6.2.4 Excitation internal parameters
Table. 6.2.4 - 382. Excitation constants.
Name
Range
Step
Default
Description
Use current to
define sync unsync
modes
0: Only BRK
statuses
1: Current and
BRK statuses
-
1:
Current
and BRK
statuses
Selects the method of defining the synchronized and
unsynchronized modes.
See also the parameter "Stator current level defining
synchronized mode".
Stator current level
defining
synchronized mode
-0.100…25.000
0.001
0.025
When "Current and BRK statuses" is selected for the
"Use current to define sync unsync modes" parameter
above, this defines the stator current threshold value.
Together with the breaker status they define the
synchronization status.
If the BRK status is ON and this threshold value is
exceeded, the status is changed to "Synchronized".
Time delay for
defining
synchronized mode
0.000…1800.000s 0.005s
0.500s
Defines the time delay that takes place before entering
the synchronized mode.
Stator current level
defining
unsynchronized
mode
–0.100…25.000
0.001
0.005
When "Current and BRK statuses" is selected for the
"Use current to define sync unsync modes" parameter
above, this defines the stator current threshold value.
If the BRK status is OFF and this threshold value is not
exceeded, the status is changed to "Unsynchronized".
Time delay for
defining
unsynchronized
mode
0.000…1800.000s 0.005s
0.100s
Defines the time delay, before entering the
unsynchronised mode.
Minimum frequency
deviation defining
Island mode
0.000…25.000Hz
0.001Hz
0.500Hz
Defines the minimum frequency deviation required to
enter the island mode.
Delay time to go to
parameters for
Island operation
0.000…1800.000s 0.005s
4.000s
Defines the delay time for entering the island mode.
Filter time for
calculation of
frequency derivative
0.000…1800.000s 0.005s
0.500s
Defines the filter time for calculation of frequency
derivative; used to detect the disturbed mode.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
459