Name
Range
Default
Description
Enable mA output channels 7
and 8
Table. 5.5.6 - 267. Settings for mA output channels.
Name
Range
Step
Default
Description
Enable mA
output
channel
0: Disabled
1: Enabled
-
0: Disabled
Enables and disables the selected mA output channel. If
the channel is disabled, the channel settings are hidden.
Magnitude
selection for
mA output
channel
0: Currents
1: Voltages
2: Powers
3: Impedance and
admittance
4: Other
-
0: Currents
Defines the measurement category that is used for mA
output control.
Magnitude
of mA
output
channel
(dependent on the
measurement
category selection)
-
(dependent on
the
measurement
category
selection)
Defines the measurement magnitude used for mA output
control. The available measurements depend on the
selection of the "Magnitude selection for mA output
channel" parameter.
Input value
1
-10
7
…10
7
0.001
0
The first input point in the mA output control curve.
Scaled mA
output
value 1
0.0000…24.0000mA 0.0001mA 0mA
The mA output value when the measured value is equal
to or less than Input value 1.
Input value
2
-10
7
…10
7
0.001
1
The second input point in the mA output control curve.
Scaled mA
output
value 2
0.0000…24.0000mA 0.0001mA 0mA
The mA output value when the measured value is equal
to or greater than Input value 2.
Figure. 5.5.6 - 179. Example of the effects of mA output channel settings.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
340
© Arcteq Relays Ltd
IM00001