Name
Range
Step
Default
KS2 compensation factor
0.00...10.00Ws/VA
0.01Ws/VA
1.00Ws/VA
KS3 signal matching factor
0.00...10.00
0.01
1.00
TW1 high-pass filter time 1
0.000...25.000s
0.005s
6.000s
TW2 high-pass filter time 2
0.000...25.000s
0.005s
6.000s
TW3 high-pass filter time 3
0.000...25.000s
0.005s
6.000s
TW4 high-pass filter time 4.(0=bypass)
0.000...25.000s
0.005s
0.000s
T1 nominator time constant of first lead/lag filter
0.000...10.000s
0.005s
1.000s
T2 denominator time constant of first lead/lag filter
0.000...10.000s
0.005s
1.000s
T3 nominator time constant of second lead/lag filter
0.000...10.000s
0.005s
1.000s
T4 denominator time constant of second lead/lag filter
0.000...10.000s
0.005s
1.000s
T7 power change integration time constant
0.000...25.000Ws/VA
0.005Ws/VA
6.000Ws/VA
T8 ramp track filter nominator time constant
0.000...25.000s
0.005s
0.400s
T9 ramp track filter denominator time constant
0.000...25.000s
0.005s
0.100s
T10 nominator time constant of third lead/lag filter
0.000...10.000s
0.005s
1.000s
T11 denominator time constant of third lead/lag filter
0.000...10.000s
0.005s
1.000s
T12 nominator time constant of fourth lead/lag filter
0.000...10.000s
0.005s
1.000s
T13 denominator time constant of fourth lead/lag filter
0.000...10.000s
0.005s
1.000s
M ramp track filter denominator exponent
1...5
1
4
N ramp track filter exponent
1...5
1
1
V
ST,max
upper limit for PSS output signal
0.00...0.20p.u.
0.01p.u.
0.05p.u.
V
ST,min
lower limit for PSS output signal
-0.20...0.00p.u.
0.01p.u.
-0.05p.u.
Reactance, Xd'
0.00...2.00p.u.
0.01p.u.
0.30p.u.
Delta calculation derivate time
0.000…25.000s
0.005s
4.000s
Delta calculation filter time
0.000…25.000s
0.005s
4.000s
Table. 6.2.1.5 - 367. PSS I/O.
Name
Range
Description
PSS external enable
(list of various inputs and outputs)
Defines an external source that enables the PSS. (1=enabled.)
PSS external block
(list of various inputs and outputs)
Defines an external source that blocks the PSS. (1=blocked.)
6.2.2 Excitation I/O
The inputs and outputs of the Generator commander are categorized as follows:
• Direct output control
• DI inputs to excitation
• PP inputs to excitation
• Bridge A I/O
• Active control status
The following subchapters, titled accordingly, go through all individual inputs and outputs in each of the
categories.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
445