Appendix C : SIA CODES
The AlphaVision NG control panel can use both the American SIA 2 protocol and the SIA HS protocol for
transmitting events. The default protocol is the SIA HS protocol. The name SIA stands for an American
committee for standardization. The regular SIA protocol is conform the American standard protocol, the
SIA HS protocol however, has a completely different modem connection. Alphatronics did this because the
regular SIA protocol is public, not secured and slow. The SIA HS protocol is encrypted, has an expanded
handshake procedure and is much faster.
Both the American SIA and the SIA HS protocol use SIA codes for transmitting the several different events.
The SIA codes used by the SIA HS protocol are the same as for the regular SIA protocol. For example,
when the system is armed, the monitoring station will always receive the SIA code “CL”, no matter if this
report was sent with the SIA HS or with the SIA protocol.
See the table below for explanation of the SIA codes. In this table all codes that are send by the AlphaVision
NG control panel are mentioned. More SIA codes exist, but these are not send by the AlphaVision NG
control panel.
AlphaVision NG installation manual Rev. 2.0 27-08-2003 Blz. 98/101
SIA
code
Definition
Description
Text message
*
ID
1
ID
2
**
AR
AC Restoral
Restore of mains
voltage
module name
module nr.
AT
AC Trouble
Mains failure
module name
module nr.
BA
Burglary Alarm
Burglary alarm
zone name
zone nr.
BB
Burglary Bypass
Bypass of a
burglary zone
zone name
zone nr.
user nr.
BR
Burglary Restoral
Restore of a
burglary zone after alarm or
tamper
zone name
zone nr.
BT
Burglary Trouble
Tamper of the
loop of a burglary zone
zone name
zone nr.
BU
Burglary Unbypass
Unbypass of a
burglary zone
zone name
zone nr.
user nr.
OP
Opening
Disarm message
Section A (fixed text for 1st section)
For 2nd up to 8th section, this text
will be Section B..H
user nr.
CI
Automatic Closing Failed
Attempt to
automatic arming by RTC failed.
Section A (fixed text for 1st section)
For 2nd up to 8th section, this text
will be Section B..H
user nr.
CL
Closing
Arm message
Section A (fixed text for 1st section)
For 2nd up to 8th section, this text
will be Section B..H
user nr.
DR
Duress
User was forced to enter
the user code at a keypad
user
nr.
FA
Fire Alarm
Fire alarm
zone name
zone nr.
FB
Fire Bypass
Bypass of a fire alarm
zone
zone name
zone nr.
user nr.
FR
Fire Restoral
Restore of a fire
alarm zone after alarm or tamper
zone name
zone nr.
FT
Fire Trouble
Tamper of the loop of
a fire alarm zone
zone name
zone nr.