<*> and <#> keys are pressed simultaneously, the programmed output will be activated and, when the SIA-
HS protocol is used, an ambush report will be transmitted to the monitoring station.
When a Yes is programmed at
Alarm after 6x wrong code
, and the SIA-HS protocol is used, a special
tamper report will be transmitted to the monitoring station when 6 times in a row a wrong code has been
entered. This report will be saved in the historic overview and, when a logprinter is used, will be printed out.
The monitoring station will receive this report as: NTA, 04, 6x ERROR CODE KP,A.
NTA stands for tamper Alarm, 04 stands for the 4
th
keypad onto which the wrong codes have been entered,
the text “6x ERROR CODE KP” is transmitted so that the monitoring understands this is not an ordinary
tamper alarm, and the A is to show that this report is connected to section A.
When separate reporting for each section is used, each section programmed to use the SIA-HS protocol, will
report this event to the monitoring station. When the historic overview is printed out, the report “6 x wrong
code” will be printed out as well.
At
Buzzer during walktest
the buzzer output as programmed in screen 5 is meant, and not the internal
keypad’s buzzer.
At
Speaker during walktest
you can program whether output 9 of the control panel and the I/O modules is
activated during the walktest. Every time a zone is activated during the walktest, the speaker will give a
short signal.
When
keyswitches are PULSE contacts
is programmed as No, all keyswitch inputs in the entire system
will function as LATCH keyswitches.
Attention:
When zones of a wireless interface module are programmed as keyswitches, this setting must be
programmed as YES!
Attention:
when zones from a wireless interface are programmed as key switch, the “keyswitches are
PULSE contacts” option MUST be programmed to ‘Yes’.
When
Medical instead of Technical
is programmed as Yes, all zones programmed as technical zones, will
function as medical zones. All alarms from these zones will be reported to the monitoring station as Medical
Alarm (MA) and Medical Restore (MR) reports. Also the reports in the LCD display and in the historical
overview will be medical reports.
When the
Final door function
is enabled, closing the last delayed zone during the exit delay will cancel the
exit delay and arm the system immediately. For example, a magnetic contact is placed on the front door,
which is programmed as a delayed zone belonging to section A. When section A is armed and the door is
closed (user exits), the last delayed zone is closed and the system will instantly arm section A.
The
A+B function
is only used in Denmark in combination with the Robofon protocol. This function must
always be programmed as “No” when the control panel is used in the Netherlands.
AlphaVision NG installation manual Rev. 2.0 27-08-2003 Blz. 49/101