5.6.2.3 Strategy 3
HINWEIS
From ControlUnit Firmware v1.40 useable
There is the possibility to convey the components in different directions and separate
them. The configuration 1 is used to separate, the configuration 2 is used for convey
the parts. The intensity can be controlled level-wise.
Input
0
1
2
3
4
5
6
7
Command
General
Release
Aux
Power
Output
Load
Config
#1
Load
Config
#2
Direction
LSB
Direction
MSB
Intensity
LSB
Intensity
MSB
The possible states are described below. The formulas for calculating the intensity and
direction can be found in the operating manual.
General Release
Status
"0"
(0V):
No release
Status
"1"
(24V):
Present release
Aux Power Output
Status
"0"
(0V):
Background lighting off, light intensity = 0%
Status
"1"
(24V):
Background lighting on, light intensity = 100%
Load Config #1
Status
"0"
(0V):
No action
Status
"1"
(24V):
With rising flank load the configuration slot "1"
Load Config #2
Status
"0"
(0V):
No action
Status
"1"
(24V):
With rising flank load the configuration slot "2"
Direction
Status
„00“
(0V,0V):
0° Conveying direction
Status
„10“
(24V,0V):
90° Conveying direction
Status
„01“
(0V,24V):
180° Conveying direction
Status
„11“
(24V,24V):
270° Conveying direction
Intensity
Status
„00“
(0V,0V):
0% Intensity = aflex switched off
Status
„01“
(0V,24V):
33% Intensity
Status
„10“
(24V,0):
66% Intensity
Status
„11“
(24V,24V):
100% Intensity