Page 70
22.10.2019
R01.43
DRV_RUNNING
Driver active, normal operating condition
STOP
Drivers stopped. Restart via "reboot" or "reinitialize" possible.
Client Node Sync State(3)
The fieldbus configuration between Profinet Node and control unit is synchronized.
This check takes place at every restart, reinitialization process or changes to the
fieldbus configuration.
SYNC
Test completed successfully, normal operating condition
ERROR_MAX_RETRY
Check failed. Maximum attempts exceeded. Check configuration.
ClientNode restart.
Fieldbus Device State(4)
Status display of the fieldbus connection
WAIT_PROCESS
Client Node is connected to the network
PROCESS_ACTIVE
There is a connection to the PLC, the data exchange is active
IDLE
PLC is in STOP mode
ERROR
Network errors (e.g., cable break)
Actual IP address (5)
Shows the actual IP address of the Profinet Modul. Is only actualized by clicking the
button “refresh”. You can’t set the IP address from the aflexConfigurator, but you can
use the Tool IP Config to do this.
Actual station name (6)
Shows the actual station Name of the Profinet Modul. Is only actualized by clicking the
button „refresh“. After clicking the button there can be a delay of 1-2 seconds until the
name is actualized. You can’t set the station name from the aflex Configurator.
reinitialize Client Node(7)
Reinitialize the client node. After changing the Fieldbus configurator this function
must executed.
INSTRUCTION
The delivered device description file is only valid when using the
standard “Profinet_Config”. Otherwise the Profinet device won’t
recognized.