10-60 ADS Manual
Problem
Event status received at customer input device from XIO
digital output is not accurate.
Possible
Causes
XIO Device
may not have been properly configured in
Qstart
for the digital output.
Possible
Solutions
Verify that the
HIGH_LEVEL
(or
HIGH_HIGH
) entity has
been selected for the appropriate digital output from the
XIO Device
in
Qstart
. Verify that
High Threshold
and
High-High Threshold
have been selected for the
Depth
Alarms
from the
MLI Device
in
Qstart
. If changes are
required, reactivate the monitor.
Contact your regional ADS representative.
Problem
Modbus communication is not successful.
Possible
Causes
Wiring to RS-485 or RS-232 port on ExPAC may be
incorrect.
Communication port settings in customer device may be
incorrect.
Modbus ID designated in
Qstart
may be incorrect.
ExPAC may be defective.
Possible
Solutions
Verify wiring for RS-485 or RS-232 is correct.
Verify that the proper communication port settings have
been set in the customer device. Port settings should
be 19200 baud, 8 data bits, no parity, 1 stop bit (8-N-1),
and no flow control.
Verify that the Modbus ID is correct
Qstart
. If the ID
requires modification, update the ID and reactivate the
monitor.
Contact your regional ADS representative.
Summary of Contents for Intrinsically-Safe TRITON+
Page 19: ...1 12 ADS TRITON Manual Control Drawing ...
Page 25: ...1 18 ADS TRITON Manual First page of the TRITON ATEX Certificate ...
Page 27: ...1 20 ADS TRITON Manual First page of the TRITON IECEx Certificate of Conformity ...
Page 29: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 1 ...
Page 30: ...Introduction 1 23 CSA Certificate of Compliance Page 2 ...
Page 32: ...Introduction 1 25 Sample TRITON Declaration of Conformity Page 2 ...