8-18
ADS
Manual
Insert one of the stripped ends of one of the wires into the
hole corresponding to
terminal 13
(or
15
) on the I/O
terminal block in the XIO.
Insert one of the stripped ends of the
other
wire into the
hole corresponding to
terminal 14
(or
16
) on the I/O
terminal block in the XIO.
I/O TERMINAL BLOCK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
1
2
1
2
I1
I2
R1
R2
+ -
+ -
+ -
+ -
NC
4-20 mA
Analogue
Outputs
4-20 mA
Analogue
Inputs
Digital
(Switch)
Inputs
Digital
(Relay)
Outputs
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
DIGITAL OUTPUT TERMINALS
Term 13 Wire
Term 14 Wire
Connecting the 2 wires from the third-party device to Terminals
13
and
14
(digital output terminals) on the I/O terminal block
Connect the other ends of the wires to the third-party
device based on the vendor’s specifications.
Close and latch the door to the XIO.
3.
Restore power to the customer’s device and the ADS XIO.