Sensor Installation and Connection
3-31
MAX ROTATION OFF
BOTTOM CENTER
OF
PIPE
CENTER
15°
15°
REQUIRES
SILT MOUNT ADAPTER
45°
Rotating the Peak Combo Sensor no more than 15 degrees up either side of
the pipe (between the 5:30 and 6:30 positions)
or
between 15 and 45
degrees up the left side of the pipe (6:30 to 7:30 position) with the silt mount
adaptor
If necessary, temporarily clear away silt to install the ring.
Restore the silt after fully securing the ring (step 7).
Make sure the ring is flat (flush) against the inside surface
of the pipe to avoid obstructing the flow or catching debris.
Verify that the Peak Combo Sensor or silt mount adapter
(
when applicable
) is flush with the pipe surface. Any
elevation of the sensor or significant deterioration or
imperfection in the pipe surface around the sensor can
create an open space in which debris can become trapped.
An elevated sensor also can misdirect the signal when
taking measurements. These vulnerabilities can quickly
result in potential damage or disruption to the sensor
and/or erroneous data.
Summary of Contents for Intrinsically-Safe TRITON+
Page 19: ...1 12 ADS TRITON Manual Control Drawing ...
Page 25: ...1 18 ADS TRITON Manual First page of the TRITON ATEX Certificate ...
Page 27: ...1 20 ADS TRITON Manual First page of the TRITON IECEx Certificate of Conformity ...
Page 29: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 1 ...
Page 30: ...Introduction 1 23 CSA Certificate of Compliance Page 2 ...
Page 32: ...Introduction 1 25 Sample TRITON Declaration of Conformity Page 2 ...