External Power
5-29
AC power cable running through cable gland with plastic nut (
ground wires
are not visible from this perspective
)
Wiring the ExPAC/XBUS/XIO to the Monitor
The last step in connecting the monitor to the external power source
involves running the external power/communication cable (ADS p/n
8000-0378-xx) and ground cable (from the
external power
grounding kit
, ADS p/n 8000-0434-xxx) between the ExPAC,
XBUS, or XIO and the monitor. One end of the external
power/communication cable has a metal connector for connection
directly into the monitor’s communication/external power port
(
COMM + EXT PWR
). The other end includes loose wires for
connecting to the terminals on the ExPAC. One end of the ground
cable has a metal ring terminal for attachment to one of the bolts on
the monitor top referred to as the
ground connection facility
. The
other end of the ground cable should have been connected to the
inside of the ExPAC enclosure, XBUS, or XIO based on the
instructions in the previous section.
Connect the ExPAC/XBUS/XIO to the monitor in the following
way:
1.
(
applicable only to the XIO and XBUS
) Loosen the plastic nut
corresponding to the middle cable gland on the bottom of the
XIO/XBUS unit.
2.
Feed the end of the communication cable with the loose wires
through the middle cable gland in the XIO/XBUS or a suitable
Summary of Contents for Intrinsically-Safe TRITON+
Page 19: ...1 12 ADS TRITON Manual Control Drawing ...
Page 25: ...1 18 ADS TRITON Manual First page of the TRITON ATEX Certificate ...
Page 27: ...1 20 ADS TRITON Manual First page of the TRITON IECEx Certificate of Conformity ...
Page 29: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 1 ...
Page 30: ...Introduction 1 23 CSA Certificate of Compliance Page 2 ...
Page 32: ...Introduction 1 25 Sample TRITON Declaration of Conformity Page 2 ...