TPU2000/2000R Modbus/Modbus Plus Automation Guide
345
2/2
Block number
2/3
Sample 0: Ia-1 (high byte)
3/1
Sample 0: Ia-1 (low byte)
3/2
Sample 0: Ib-1 (high byte)
3/3
Sample 0: Ib-1 (low byte)
4/1
Sample 0: Ic-1 (high byte)
4/2
Sample 0: Ic-1 (low byte)
4/3
Sample 0: In-1 (high byte)
5/1
Sample 0: In-1 (low byte)
5/2
Sample 0: Ia-2 (high byte)
5/3
Sample 0: Ia-2 (low byte)
6/1
Sample 0: Ib-2 (high byte)
6/2
Sample 0: Ib-2 (low byte)
6/3
Sample 0: Ic-2 (high byte)
7/1
Sample 0: Ic-2 (low byte)
7/2
Sample 0: Ig-2 (high byte)
7/3
Sample 0: Ig-2 (low byte)
8/1 - 13/1
Sample 1 data
13/2 - 18/2
Sample 2 data
18/3 - 23/3
Sample 3 data
24/1 - 29/1
Sample 4 data
29/2 - 34/2
Sample 5 data
34/3 - 39/3
Sample 6 data
40/1 - 45/1
Sample 7 data
45/2
Spare
45/3
Spare
14.6 Fetch Next Block of a Record-Part A ( 3 14 6 )
Same message format as ( 3 14 5 )
14.7 Retransmit Last Block of a Record-Part A ( 3 14 7 )
Same message format as ( 3 14 5 )
14.8 Fetch First Block of a Record-Part B ( 3 14 8 )
Msg Byte Definition
1/1
Relay status (see command 3 4 1, msg 1/1)
1/2
C Subcommand = 0xe8
1/3
Total Number of Messages = 9
2/1
Record number
2/2
Block number
2/3
Phase scale Wdg 1 (high byte)
3/1
Phase scale Wdg 1 (low byte)
3/2
Neutral scale Wdg 1 (high byte)
3/3
Neutral scale Wdg 1 (low byte)
4/1
Phase scale Wdg 2 (high byte)
4/2
Phase scale Wdg 2 (low byte)
4/3
Ground scale Wdg 2 (high byte)
5/1
Ground scale Wdg 2 (low byte)
5/2
Input status (high byte)
5/3
Input status (low byte)
6/1
Output status (high byte)
6/2
Output status (low byte)
Bit 0: Differential Trip
Bit 1: Trip failure
Bit 2: Through Fault
Bit 3: 2nd Harmonic Restraint