TPU2000/2000R Modbus/Modbus Plus Automation Guide
293
25/2
I2-2 Angle Lo byte
25/3
Spare
26/1-29/3
Reserved for Tap Changer Position
5.2 Show Demand Currents Data ( 3 5 2 )
Msg byte Definition
1/1
Relay Status (see command 3 4 1, msg 1/1)
1/2
C Subcommand = 0x52
1/3
Total Number of Messages = 6
2/1
Aux. Status byte (see command 3 5 1, msg 2/1)
2/2
Demand Ia Hi byte (Load Currents)
2/3
Demand Ia Mid byte
3/1
Demand Ia Lo byte
3/2
Demand Ib Hi byte
3/3
Demand Ib Mid byte
4/1
Demand Ib Lo byte
4/2
Demand Ic Hi byte
4/3
Demand Ic Mid byte
5/1
Demand Ic Lo byte
5/2
Demand In/Ig Hi byte
5/3
Demand In/Ig Mid byte
6/1
Demand In/Ig Lo byte
6/2
Spare
6/3
Spare
5.3 Show Maximum Demand Currents Data ( 3 5 3 )
Msg byte Definition
1/1
Relay Status (see command 3 4 1, msg 1/1)
1/2
C Subcommand = 0x53
1/3
Total Number of Messages = 12
2/1
Aux. Status byte (see command 3 5 1, msg 2/1)
2/2
Max Dem Ia Hi byte (Load Currents)
2/3
Max Dem Ia Mid byte
3/1
Max Dem Ia Lo byte
3/2
Max Dem Ia time yy
3/3
Max Dem Ia time mn
4/1
Max Dem Ia time dd
4/2
Max Dem Ia time hh
4/3
Max Dem Ia time mm
5/1
Max Dem Ib Hi byte
5/2
Max Dem Ib Mid byte
5/3
Max Dem Ib Lo byte
6/1
Max Dem Ib time yy
6/2
Max Dem Ib time mn
6/3
Max Dem Ib time dd
7/1
Max Dem Ib time hh
7/2
Max Dem Ib time mm
7/3
Max Dem Ic Hi byte
8/1
Max Dem Ic Mid byte
8/2
Max Dem Ic Lo byte
8/3
Max Dem Ic time yy
9/1
Max Dem Ic time mn
9/2
Max Dem Ic time dd
9/3
Max Dem Ic time hh
10/1
Max Dem Ic time mm
10/2
Max Dem In/Ig Hi byte
10/3
Max Dem In/Ig Mid byte