One 4X register at the beginning of the 4X control register groups is read only which feeds back the status of
password control which was configured via Registers 62560 through 62598 (Security Mask Control Block) or via
the Communications Configuration Screen accessible through ECP or WinECP. The register lists the six control
blocks found in the TPU2000/TPU2000R. Table 5-41 lists the Security Mask register, which reports, which of the
control blocks require password control. A status of 1 in the defined bit location allows any value to be placed in
the password field (as shown in Table 5-42). The Security mask status of what was programmed through ECP,
WinECP or Modbus Registers 62560 through 62598 may be obtained by reading Register 41409. A status of 0 in
the defined field requires the correct password to be sent as part of the control process.
Figure 5-43 illustrates the Group Blocks within the TPU2000/TPU2000R and its associated typical control register
mapping.
Execute Register
Password Char 1
Password Char 2
Password Char 3
Password Char 4
Control Mask 1
Copy of Control Mask 1
Initiate Inputs
Force Phys. In
Force Phys. Out.
Force Log. In
Set/Reset Outputs
Pulse Outputs
Typical Definition
EC
Of a Control Block
Command
Sequence Through
Modbus Command 16
Preset Multiple Holding Registers
Security Status
= Read Only Register
41409
41410
41457
Figure 5-43. Typical Control Features Available for the TPU2000 and TPU2000R
Table 5-41. Security Status Register Indicating Password Requirement
Register Item
Description
41409
16 Bit Unsigned Security Mask (Read Only, See Register 6XXXX for setup
or refer to ECP or WinECP Configuration Program)
Bit 0 (lsb)
Initiate Input (GROUP I) Password Required
Bit 1
Force Physical Input (GROUP II) Password Required
Bit 2
Force Physical Output (GROUP III) Password Required
Bit 3
Force Logical Input (GROUP IV) Password Required
Bit 4
Set/ Reset Outputs (GROUP V) Password Required
Bit 5
Pulse Outputs (GROUP VI) Password Required
Bit
6
Reserved
Bit
7
Reserved
Bit
8
Reserved
Bit
9
Reserved
Bit
10
Reserved
Bit
11
Reserved
Bit
12
Reserved
Bit
13
Reserved
Bit
14
Reserved
Bit 15 (msb)
Reserved
One method to perform control through the Control Block is as follows:
•
Write all registers other than the register associated with the “Execute Register”
•
Write a “1” to execute the control command.