TPU2000/2000R Modbus/Modbus Plus Automation Guide
211
61674
Phase Demand
Unsigned Integer
0<=Range <=9999
61675
Neutral Demand
Unsigned Integer
0<=Range <=9999
61676
Load Current Alarms
Unsigned Integer 16 Bits
0<=Range <=9999
61677
3 Phase Demand Alarm
Unsigned Integer 16 Bits
10<=Range <=9999 , 10000 Disables
61678
Low PF Alarm
Unsigned Integer 16 Bits
0.5<=Range <=1.0 *100 , 101 Disables
61679
High PF Alarm
Unsigned Integer 16 Bits
0.5<=Range <=1.0 *100 , 101 Disables
61680
Positive KVAR Alarm
Unsigned Integer 16 Bits
10<=Range <=99990/10 , 10000 Disables
61681
Negative KVAR Alarm
Unsigned Integer 16 Bits
10<=Range <=99990/10 , 10000 Disables
61682
Positive Watt Alarm 1
Unsigned Integer 16 Bits
0<=Range <=9999 , 10000 Disables
62683
Positive Watt Alarm 2
Unsigned Integer 16 Bits
0<=Range <=9999 , 10000 Disables
Table 5-76. 3 Winding Alarm Settings Block
Register
Address
Item Description
63840 SPARE_1
63841 Execute
Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
Unsigned 16 Bits
63842
Access Password
ASCII – 2 Characters Leftmost Digits
63843
Access Password
ASCII – 2 Characters Rightmost Digits
63844 SPARE_2
63845
Positive Watt Alarm 2
Unsigned Integer 16 Bits
0<=Range <=9999 , 10000 Disables
63846
Through Fault Summation KSI
Alarm – Winding 3.
Unsigned Integer 16 Bits
0<=Range <=9999
Real Time Clock (13 Registers Defined)
The real time clock data can be set via the network. This clock is the master which is used to time stamp
operational records and event records in Registers 41029 through 41036 (as defined in Table 17) and Registers
41284 through 41291 (as defined in Table 20). It should be noted that the clock registers have been updated to
reflect the four digit year required for Y2K compliance in time reporting.
If the month is set to 0, the real time clock is disabled.
The real time clock cannot be enabled or disabled via
Modbus. The real time clock may only be disabled via TPU2000/TPU2000R Standard 10 Byte Protocol
Attached hereto and referenced in Appendix A.
Table 5-77 lists the register definition for Real Time Clock configuration.
Table 5-77. Real Time Clock Register Definition Assignment
Register
Address
Item Description
61792 SPARE_1
61793 Execute
Register
0 = No Action
Unsigned 16 Bits