TPU2000/2000R Modbus/Modbus Plus Automation Guide
131
One should note the operation record event codes are arranged in groups to easily indicate the type of error
dependent on the value of the operation record. Table 5-39 lists the Operation Record Event Codes.
Table 5-39. Operation Record Address Definition
Register
Address
Item Description
42049 EvtRecCtlReg
1 = First Record
2 = Next Record
3 = Last Unreported Record
Fault Record Control Register
Unsigned 16 Bit
1 = Fill 42050 – 42059 with First Record Data.
2 = Fill 42050 – 42059 with next Record Data pointed to in
buffer.
3 = Fill 42050 – 42059 with the last unreported record of
data between the last data access
42050
Year (0-99)
Unsigned 16 Bit Year of Event
42051
Month
Unsigned 16 Bit Month of Event
42052
Day
Unsigned 16 Bit Day of Event
42053
Hour
Unsigned 16 Bit Hour of Event
42054
Minute
Unsigned 16 Bit Minute of Event
42055
Second
Unsigned 16 Bit Second of Event
42056
Hundredths of a Second
Unsigned 16 Bit Hundredth Second of Event Date
42057
Message Number
Unsigned Integer 16 Bits 0<=Range <=999
42058
VALUE ?
Who the hell knows?
42059 Operation
Number
16 Bit Unsigned
See Table XX
Table 5-40. Event Record Definition Type
Event Record Type (Register 42058 code definition)
Operation Number
Definitions
00
87TTrip
01
87H
Trip
02
51P-1
Trip
03
51N-1
Trip
04
50P-1
Trip
05
50N-1
Trip
06
150P-1
Trip
07
150N-1
Trip
08
46-1
Trip
09
51P-2
Trip
10
51G-2
Trip
11
50P-2
Alarm
12
50G-2
Alarm
13
150P-2
Block
14
150G-2
Trip
15
46-2
Restore
16
ECI-1
17
ECI-2
18
Through
Fault
19
Harmonic
Rest
31
Fault
Clear
Failed
32
Fault
Cleared
33
Harmonic
Restraint
34
Manual
Trip
35
Manual
Trip
Failed
40
87T
Enabled
41
87H
Enabled
42
51P-1
Enabled
Summary of Contents for TPU2000