TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
336
24/2
Spare
24/3
Spare
25/1
Spare
25/2
Checksum (high byte)
25/2
Checksum (low byte)
13.8 Receive Differential Curve Parameters ( 3 13 8 )
For the unit to receive the differential curve data, the following sequence of commands must be issued:
3 13 8 (Differential Curve Parameters)
3 13 9 (Operate Threshold Data Points) Block 0
3 13 10 (Operate Threshold Data Points) Block 1
3 13 10 (Operate Threshold Data Points) Block 2
Data Byte Definition
1/1
Most significant high byte of password
1/2
Most significant low byte of password
1/3
Least significant high byte of password
2/1
Least significant low byte of password
2/2
Spare
2/3
C Subcommand = 0xd8
3/1
Programmable curve number (1, 2, or 3)
3/2
Coefficient A (high high byte)
3/3
Coefficient A |
4/1
Coefficient A |
4/2
Coefficient A (low low byte)
4/3
Coefficient B (high byte)
5/1
Coefficient B |
5/2
Coefficient B |
5/3
Coefficient B (low byte)
6/1
Coefficient C (high byte)
6/2
Coefficient C |
6/3
Coefficient C |
7/1
Coefficient C (low byte)
7/2
Spare
7/3
Spare
8/1
Spare
8/2
Spare
8/3
Spare
9/1
Spare
9/2
Checksum (high byte)
9/3
Checksum (low byte)
13.9 Receive First Differential Curve Data Set ( 3 13 9 )
Data Byte Definition
1/1
Most significant high byte of password
1/2
Most significant low byte of password
1/3
Least significant high byte of password
2/1
Least significant low byte of password
2/2
Spare
2/3
C Subcommand = 0xd9
3/1
Programmable
curve
number (1, 2, or 3)
3/2
Data Point 0: Operate Threshold (high byte)
3/3
Data Point 0: Operate Threshold (low byte)
4/1
Data Point 1: (same as Data Point 0)
4/2
Data Point 1: (same as Data Point 0)
4/3
Data Point 2: (same as Data Point 0)