TPU2000/2000R Modbus/Modbus Plus Automation Guide
201
Register
Address
Item Description
Bit 12: Reserved
Bit 13: Reserved
Bit 14: Reserved
Bit 15: Reserved (msb) (leftmost bit)
If a 3 Winding Relay is used, Alternate Settings Table Definitions are given in Table 5-69 Below:
Table 5-69. Alternate 1 Settings For 3 Winding Block
Register
Address
Item Description
63328 SPARE_1
63329 Execute
Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
Unsigned 16 Bits
63330
Access Password
ASCII – 2 Characters Leftmost Digits
63331
Access Password
ASCII – 2 Characters Rightmost Digits
63332 SPARE_2
63333
87T-3 Amp
Unsigned Integer 16 Bits
2<=Range<=9 (X10)
0.4<=Range<=1.8 (X50)
63334
51P-3 Curve Select (TYPE I)
Unsigned 16 Bits
Range 0-12 (See Text Above)
63335
51P-3 Pickup Amps
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
63336
51P-3 Time Dial/Time Delay
Unsigned 16 Bits
1<=Range <=10 (X20) Time Dial
0<=Range<=10 (X20) Time Delay
63337
50P-3 Curve Select Byte (TYPE II) Unsigned Integer 16 bits
0<=Range<=12 (See Text Above)
63338
50P-3 Pickup Amps
Unsigned 16 Bits
0.5<=Range<= 20 *10
63339
50P-3 Time Dial/Time Delay
U
U
n
n
s
s
i
i
g
g
n
n
e
e
d
d
1
1
6
6
B
B
i
i
t
t
s
s
Dial *10
Delay * 100
63340
150P-3 Curve Select
Unsigned Integer 16 bits
See Table Above
63341
150P-3 Pickup Amps
Unsigned 16 Bits
0.5<=Range<= 20 *10
63342
150P-3 Time Dial
Unsigned 16 Bits
0<=Range<=9.99 * 100
63343
46-3 Curve Select Byte
Unsigned Integer 16 bits
See Table Above
63344
46-3 Pickup Amps
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
63345
46-3 Time Dial/ Time Delay
Unsigned 16 Bits
1<=Range<=12 * 10
0.2<=Range<= 0.4 *50
63346
51N-3 Curve Select (TYPE II)
Unsigned 16 Bits
Range 0-12 (See Text Above)
63347
51N-3 Pickup Amps
Unsigned 16 Bits
1<=Range<= 12 *10
Summary of Contents for TPU2000
Page 10: ......