TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
330
5/3
OUT 3 delay high byte (0.00-60, *100)
6/1
OUT 3 delay low byte
6/2
OUT 2 delay high byte (0.00-60, *100)
6/3
OUT 2 delay low byte
7/1
OUT 1 delay high byte (0.00-60, *100)
7/2
OUT 1 delay low byte
7/3
Spare
8/1
Spare
8/2
Spare
8/3
Spare
9/1
Spare
9/2
Checksum high byte
9/3
Checksum low byte
13 Programmable Curve Commands ( 3 13 n )
N Definition
0
Reserved for repeat 3 13 n
1
Receive Overcurrent Curve Parameters
2
Receive First Overcurrent Curve Data Set
3
Receive Next Overcurrent Curve Data Set
4 Receive
Overcurrent Curve Pointer Table
5
Send Overcurrent Curve Parameters
6
Send Overcurrent Curve Data Set
7
Send Overcurrent Curve Pointer Table
8
Receive Differential Curve Parameters
9
Receive First Differential Curve Data Set
10
Receive Next Differential Curve Data Set
11
Send Differential Curve Parameters
12
Send Differential Curve Data Set
13.1 Receive Overcurrent Curve Parameters ( 3 13 1 )
For the unit to receive the overcurrent curve data, the following sequence of commands must be issued:
3 13 1 (Curve Parameters)
3 13 2 (8 Alpha-Beta segments) Block 0
3 13 3 (8 Alpha-Beta segments) Block 1
3 13 3 (8 Alpha-Beta segments) Block 2
3 13 3 (8 Alpha-Beta segments) Block 3
3 13 3 (8 Alpha-Beta segments) Block 4
3 13 3 (8 Alpha-Beta segments) Block 5
3 13 3 (8 Alpha-Beta segments) Block 6
3 13 4 (60 Pointer Offsets)
Data Byte Definition
1/1
Most significant high byte of password
1/2
Most significant low byte of password
1/3
Least significant high byte of password
2/1
Least significant low byte of password
2/2
Spare
2/3
C Subcommand = 0xd1
3/1
Programmable curve number
User Programmable Curve number: 1=User 1; 2=User 2; 3=User 3
3/2
Coefficient A (high high byte)
3/3
Coefficient A |
4/1
Coefficient A |
4/2
Coefficient A (low low byte)
4/3
Coefficient B (high byte)
Summary of Contents for TPU2000
Page 10: ......