TPU2000/2000R Modbus/Modbus Plus Automation Guide
147
3. The default list corresponds to the Logical Input mapping of Logical Inputs (hereto referred as LI) as
illustrated in Table 5-47.
4. If one would wish to change the relay protective function element mapped to the specific LI, depress
the “ENTER” key. The display in Figure 5-55 shall result.
5. The user would then scroll down the list and highlight the element desired to be mapped to the
specific LI within the edited list.
6. Depress the “ENTER” key to map the selected element into the table.
Figure 5-54. ECP Default Logical Input List
Table 5-47. ECP Default Correlation to Forced Logical Input Bit Map
FLI
Number
Description User
Name
FLI
Number
Description User
Name
FLI 01
3 Phase % Diff. Current Control
87 T
FLI 17
Alternate Settings 1 Enable
ALT 1
FLI 02
3 Phase Inst. Differential Current
Control
87H
FLI 18
Alternate Settings 2 Enable
ALT 2
FLI 03
Winding 1 Phase Time
Overcurrent Control
51P-1
FLI 19
Event Capture Initiate 1
ECI 1
FLI 04
Winding 2 Phase Time
Overcurrent Control
51P-2
FLI 20
Event Capture Initiate 2
ECI 2
FLI 05
Winding 1 Neutral Time
Overcurrent Control
51N-1
FLI 21
Waveform Capture Initiate
WCI
FLI 06
Winding 2 Ground Time
Overcurrent Control Winding 2
51G-2
FLI 22
Differential Trip Output
Contact Enable
TRIP
FLI 07
Phase Instantaneous Level 1
Enable Winding 1
50P-1
FLI 23
Sudden Pressure
SPR
FLI 08
Phase Instantaneous Level 1
Enable Winding 2
50P-2
FLI 24
Trip Coil Monitor Enable
TCM
FLI 09
Neutral Instantaneous Level 1
Enable Winding 1
50N-1
FLI 25
User Logical Input 1
ULI 1
FLI 10
Ground Instantaneous Level 1
Enable Winding 2
50G-2
FLI 26
User Logical Input 2
ULI 2