TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
324
5 = Long Time Extremely Inverse
6 = Long Time Very Inverse
7 = Long Time Inverse
8 = Recloser Curve
9 = Disabled
10 = User Curve 1
11 = User Curve 2
12 = User Curve 3
Curve Selection Type II
0 = Disabled
1 = Standard
2 = Inverse
3 = Definite Time
4 = Short Time Inverse
5 = Short Time Extremely Inverse
6 = User Curve 1
7 = User Curve 2
8 = User Curve 3
Curve Selection Type 87T
0 = Disabled
1 = Percent Slope
2 = HU 30%
3 = HU 35%
4 = Percent 15 Tap
5 = Percent 25 Tap
6 = Percent 40 Tap
7 = User Curve 1
8 = User Curve 2
9 = User Curve 3
Mode Selection Type 87T
0 = Disabled
1 = 2nd Harmonics
2 = 2nd & 5th Harmonics
3 = All Harmonics
Msg byte Definition
1/1
Most significant high byte of password
1/2
Most significant low byte of password
1/3
Least significant high byte of password
2/1
Least significant low byte of password
2/2
spare
2/3
C Subcommand = (Prim=0xb8, Alt1=0xb9, Alt2=0xba)
3/1
87T Curve Select byte (Type 87T)
3/2
87T Min I Operate byte (0.2-1.0 *10)
3/3
87T Percent Restraint byte (15-60)
4/1
87T Restraint Mode byte (Mode Selection Type 87T)
4/2
87T 2nd Harmonic Restraint high byte (7.5-25 *10)
4/3
87T 2nd Harmonic Restraint low byte
5/1
87T 5th Harmonic Restraint high byte (15-40 *10)
5/2
87T 5th Harmonic Restraint low byte
5/3
87T All Harmonics Restraint high byte (15-40 *10)
6/1
87T All Harmonics Restraint low byte
6/2
87H Tap X byte (6-20 *10)
6/3
87T-1 Tap Amp byte (2-9 Amp *10, 0.4-1.8 Amp *50)
7/1
51P-1 Curve Select byte (Type I)
7/2
51P-1 Pickup Amp/OA (1-12A *10, 0.2-2.4A *50)
Summary of Contents for TPU2000