TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
304
6 Load Profile Commands & Records ( 3 6 n )
N
Definition
0
Define Load Profile Settings
1
Start Load Profile Data Accumulation
2
Freeze Load Profile Data
3
Report Load Profile Header-All
4
Report Next Load Profile Data Block
5
Retransmit Last Load Profile Data Block
6
Report Load Profile Header-Last
7
Not
in
use
8
Fault
Record-First
9
Fault
Record-Next
10
Restraint
Record-First
11
Restraint
Record-Next
12
Oldest Unreported Differential Record
13
Oldest Unreported Through Fault Record
14
Oldest
Unreported
Harmonic Restraint Record
15
Oldest Unreported Operations Record
6.0
Load Profile Settings ( 3 6 0 )
Reserved for user configuration.
6.1
Accumulate Load Profile Data ( 3 6 1 )
6.2
Freeze Load Profile Data ( 3 6 2 )
6.3
Report Load Profile Data Header(All Data) ( 3 6 3 )
This command is used to initialize the unit to report the entire contents of the accumulated load profile.
Msg byte Definition
1/1
Relay Status (see command 3 4 1, msg 1/1)
1/2-4/1
Report Column (1-9) Attribute Number
4/2
spare
4/3-9/3
Unit Id Name (16 chars)
10/1-11/2
Time Tag of the first Block reporting (5 bytes :yy,mn,dd,hh,mm in order)
11/3
spare
12/1-12/2
Report Column 1 Attribute Scale(high, low byte)
12/3-17/3
Report Column (2-9) Attribute Scale
Attr#
Description Dynamic
Scale
0 Demand
Ia
1
1 Demand
Ib
1
2 Demand
Ic
1
3 Demand
In
1
6.4
Report Next Load Profile Data Block ( 3 6 4 )
Msg byte Definition
1/1
Demand Interval (5/15/30/60 Mins)
1/2-1/3
Record # (a number starting from 1 to #of blocks)
2/1
Total Number Data Bytes (1 through 126)
2/2-3/3
Time Tag of the first Block (5 bytes : hh, mm, dd, mn, yy in order)
NOTE: Different order from command 3 6 3 time stamp.
4/1-45/3
Data Blocks (up to 126 bytes of data)