TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
334
8/1
Spare
8/2
Checksum (high byte)
8/3
Checksum low byte)
13.6 Send Overcurrent Curve Data Set ( 3 13 6 )
Data Byte Definition
1/1
User Programmable Curve number: 1=User 1; 2=User 2; 3=User 3
1/2
Block number
1/3
Programmable curve Block number
Msg Byte Definition
1/1
Relay Status (see command 3 4 1, msg 1/1)
1/2
C Subcommand = 0xd6
1/3
Total Number of Messages = 29
2/1
Programmable
curve
number
User Programmable Curve number: 1=User 1; 2=User 2; 3=User 3
2/2
Block
number
2/3
Segment 0: Endrange (high byte)
3/1
Segment 0: Endrange (low byte)
3/2
Segment 0: Alpha (high byte)
3/3
Segment 0: Alpha |
4/1
Segment 0: Alpha |
4/2
Segment 0: Alpha (low byte)
4/3
Segment 0: Beta (high byte)
5/1
Segment 0: Beta |
5/2
Segment 0: Beta |
5/3
Segment 0: Beta (low byte)
6/1-9/1
Segment 1 (same as segment 0)
9/2-12/2
Segment 2 (same as segment 0)
12/3-15/3
Segment 3 (same as segment 0)
16/1-19/1
Segment 4 (same as segment 0)
19/2-22/2
Segment 5 (same as segment 0)
22/3-25/3
Segment 6 (same as segment 0)
26/1-29/1
Segment 7 (same as segment 0)
29/2
Checksum
(high
byte)
29/3
Checksum (low byte)
13.7 Send Overcurrent Curve Pointer Table ( 3 13 7 )
Data Byte Definition
1/1
Programmable curve number
User Programmable Curve number: 1=User 1; 2=User 2; 3=User 3
1/2
Programmable curve number
1/3
Programmable curve number
Msg Byte Definition
1/1
Relay Status (see command 3 4 1, msg 1/1)
1/2
C Subcommand = 0xd7
1/3
Total Number of Messages = 25
2/1
Programmable curve number
User Programmable Curve number: 1=User 1; 2=User 2; 3=User 3
2/2
Pointer offset 0
2/3
Pointer offset 1
3/1
Pointer offset 2
3/2
Pointer offset 3
3/3
Pointer offset 4
4/1
Pointer offset 5
4/2
Pointer offset 6
Summary of Contents for TPU2000