TPU2000/2000R Modbus/Modbus Plus Automation Guide
151
Bit 5 FLI 22
1 = Force State 0 = Normal State
Bit 6 FLI 23
1 = Force State 0 = Normal State
Bit 7 FLI 24
1 = Force State 0 = Normal State
Bit 8 FLI 25
1 = Force State 0 = Normal State
Bit 9 FLI 26
1 = Force State 0 = Normal State
Bit 10 FLI 27
1 = Force State 0 = Normal State
Bit 11 FLI 28
1 = Force State 0 = Normal State
Bit 12 FLI 29
1 = Force State 0 = Normal State
Bit 13 FLI 30
1 = Force State 0 = Normal State
Bit 14 FLI 31
1 = Force State 0 = Normal State
Bit 15 FLI 32 (msb)
1 = Force State 0 = Normal State
41439
Force Logical Input State Mask
FLI 01 – FLI 16
Unsigned (16 Bits)
Bit 0 FLI 01 (lsb)
1 = Force Set State 0 = Force Reset State
Bit 1 FLI 02
1 = Force Set State 0 = Force Reset State
Bit 2 FLI 03
1 = Force Set State 0 = Force Reset State
Bit 3 FLI 04
1 = Force Set State 0 = Force Reset State
Bit 4 FLI 05
1 = Force Set State 0 = Force Reset State
Bit 5 FLI 06
1 = Force Set State 0 = Force Reset State
Bit 6 FLI 07
1 = Force Set State 0 = Force Reset State
Bit 7 FLI 08
1 = Force Set State 0 = Force Reset State
Bit 8 FLI 09
1 = Force Set State 0 = Force Reset State
Bit 9 FLI 10
1 = Force Set State 0 = Force Reset State
Bit 10 FLI 11
1 = Force Set State 0 = Force Reset State
Bit 11 FLI 12
1 = Force Set State 0 = Force Reset State
Bit 12 FLI 13
1 = Force Set State 0 = Force Reset State
Bit 13 FLI 14
1 = Force Set State 0 = Force Reset State
Bit 14 FLI 15
1 = Force Set State 0 = Force Reset State
Bit 15 FLI 16 (msb)
1 = Force Set State 0 = Force Reset State
A simple application example in Figure 5-56 follows, illustrating the method to force TPU2000 or TPU2000R
functions via the Group IV mapping.
EC
Command
Sequence Through
Modbus Command 16
Preset Multiple Holding Registers
STEP 1 -
Host sends following register contents
to initiate FLI 12 ( Mapped To ZSC) and FLI 25 (Mapped to
ULO2) ( Assumed that defaultpassword of all spaces
is active).
41431 = 2020 hex (Password Hi)
41432 = 2020 hex (Password Lo)
41433 = 0 (Reserved)
41434 = 0200 hex (Select FLI 25 Bit to Change)
41435 = 0800 hex ( Select FLI 12 Bit to Change).
41436 = 0200 hex ( Select FLI 25 Force State)
41437 = 0800 hex ( Select FLI 12 Force State)
41438 = 0200 hex ( Set FLI 25 Bit to State of 1)
41439 = 0800 hex ( Set FLI 12 Bit to State of 1)
EXAMPLE 4 - Enable 150P- 2Control and UL1 1 which is mapped to a
Physical Output via the ECP PHYSICAL OUTPUT MAP.
EC
The relay forces FLI 25 and FLI 12 to be a value of 1 Forced.
The TPU 2000R is mapped via the Change Logical Input Screen.
A Modbus response will be returned to the host
indicating that the command has been accepted.
EC
Command
Sequence Through
Modbus Command 16
Preset Multiple Holding Registers
STEP 2 -
The host sends the register execute
command to the following address
with the following contents.
41430 = 0001 hex
EC
The Relay Responds over the network
that the command has been accepted.
Figure 5-56. Application Example Illustrating the Use of FLI Group IV Methodology
Summary of Contents for TPU2000