TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
276
16
ALT1
Enables Alt 1 Settings
17
ALT2
Enables Alt 2 Settings
18
ECI1
Event-1 Capture Initiated
19
ECI2
Event-2 Capture Initiated
20
WCI
Waveform Capture Initiated
21
Trip
Initiates Diff Trip Output
22
SPR
Sudden Pressure Input
23
TCM
Trip Coil Monitoring
24
ULI1
User Logical Input 1
25
ULI2
User Logical Input 2
26
ULI3
User Logical Input 3
27
ULI4
User Logical Input 4
28
ULI5
User Logical Input 5
29
ULI6
User Logical Input 6
30
ULI7
User Logical Input 7
31
ULI8
User Logical Input 8
32
ULI9
User Logical Input 9
33
CRI
Clears Through Fault and OC Counters
Example : if message
2/1 = hex 24
2/2 = hex 11
2/3 = hex 4
I/O word is 00100100 00010001 hex 2411
Note the Physical Inputs are translated using the physical input table below: In the example IN3, IN10, IN8 and IN5 are
selected for GND.
The AND/OR selection and enable disable mapping is selected with commands 3 11 3 and 3 11 2
Bit
Physical Input
---
--------------
0
IN6
1
IN7
2
IN8
3
IN2
4
IN9
5
IN3
6
IN4
7
IN5
8
IN1
9
Reserved
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
Msg byte Definition
1/1
Relay Status
Bit 0 : SelfTest Status
Bit 1 : Contact Input Status changed
Bit 2 : Local Settings Change
Bit 3 : Remote Edit Disabled.
Bit 4 : Alternate Settings Group 1 enabled.
Bit 5 : Alternate Setting Group 2 enabled.
Bit 6 : Fault Record Logged.
Bit 7 : Power was Cycled
1/2
C Subcommand = 0x41