TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
294
11/1
Max Dem In/Ig Lo byte
11/2
Max Dem In/Ig time yy
11/3
Max Dem In/Ig time mn
12/1
Max Dem In/Ig time dd
12/2
Max Dem In/Ig time hh
12/3
Max Dem In/Ig time mm
5.4 Show Minimum Demand Currents Data ( 3 5 4 )
Msg byte Definition
1/1
Relay Status (see command 3 4 1, msg 1/1)
1/2
C Subcommand = 0x53
1/3
Total Number of Messages = 12
2/1
Aux. Status byte (see command 3 5 1, msg 2/1)
2/2
Min Dem Ia Hi byte (Load Currents)
2/3
Min Dem Ia Mid byte
3/1
Min Dem Ia Lo byte
3/2
Min Dem Ia time yy
3/3
Min Dem Ia time mn
4/1
Min Dem Ia time dd
4/2
Min Dem Ia time hh
4/3
Min Dem Ia time mm
5/1
Min Dem Ib Hi byte
5/2
Min Dem Ib Mid byte
5/3
Min Dem Ib Lo byte
6/1
Min Dem Ib time yy
6/2
Min Dem Ib time mn
6/3
Min Dem Ib time dd
7/1
Min Dem Ib time hh
7/2
Min Dem Ib time mm
7/3
Min Dem Ic Hi byte
8/1
Min Dem Ic Mid byte
8/2
Min Dem Ic Lo byte
8/3
Min Dem Ic time yy
9/1
Min Dem Ic time mn
9/2
Min Dem Ic time dd
9/3
Min Dem Ic time hh
10/1
Min Dem Ic time mm
10/2
Min Dem In/Ig Hi byte
10/3
Min Dem In/Ig Mid byte
11/1
Min Dem In/Ig Lo byte
11/2
Min Dem In/Ig time yy
11/3
Min Dem In/Ig time mn
12/1
Min Dem In/Ig time dd
12/2
Min Dem In/Ig time hh
12/3
Min Dem In/Ig time mm
5.5 Show Magnitudes Load Metered Data ( 3 5 5 )
Msg byte Definition
1/1
Relay Status (see command 3 4 1, msg 1/1)
1/2
C Subcommand = 0x55
1/3
Total Number of Messages = 6
2/1
Aux. Status byte (see command 3 5 1, msg 2/1)
2/2
Ia high byte (Load Currents)
2/3
Ia (mid byte)
3/1
Ia (low byte)
3/2
Ib (high byte)
3/3
Ib (mid byte)